Lennox International Inc G32Q3-75 j,AP, Condensate Plumbing, groundjoint type, Left Side Piping

Models: G32Q4-100 G32Q4-125 G32Q3-75 G32Q5-125 G32Q5-100 G32Q3-100

1 32
Download 32 pages 3.21 Kb
Page 15
Image 15
CONDENSATE PLUMBING

CONDENSATE PLUMBING

(Plumbing must be vented higher than coll.)

3 - The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb wait-

ers or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. When

left-hand gas plumbing is required, gas line should be installed in the lower half of knockout so that pip- ing will clear combustion air inducer. See figure 24.

4 - The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the fur- nace. The piping must be supported at properinter- vals [every 8to 10 feet (2.44 to 3.01 m) using suitable hangers or straps. A drip leg should be installed in vertical pipe runs to the unit.

5 - Some local codes may require installationof a manu- al main shut-off valve and union (furnished by the in- staller) external to the unit. Union must be of the

groundjoint type,

FIGURE 22

6- Connect condensate drain line (1/2 inch [13 mm] SDR 11 plastic pipe or tubing) to condensate con- nection on condensate trap assembly and route to open drain. Condensate line must be sloped down- ward away from drip leg to drain. If the drain level is above condensate outlet, use a condensate pump to

pump the condensate to the higher level. Conden- sate drain line should be routed within the condi-

tioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate line. Heat- ing cable kit is available from Lennox in various lengths; 6 feet (1.8 m) - kit no. 18K48; 24 feet (7.3 m) - kit no. 18K49; and 50 feet (15.2 m) - kit no. 18K50.

1 - Gas piping may be muted into the unitthrough either the left- or right-hand side. Supply piping enters into the gas valve from the bottom of the valve as shown in figure 24.

2- When connecting the gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 5 lists recommended pipe sizes for typi- cal applications.

NOTE - Use two wrenches when connecting gas pip- ing to avoid transferring torque to the manifold.

II

CAP-_D-I_IU

FIGURE 23

NOTE - Install a 1/8 inch NPTplugged tap in the field pip ing upstream ofthe gas supplyconnection to the unit. The tap must be accessible for test gauge connection. See figure 24.

LEFT SIDE PIPING

MANUAL MAIN

SHUT-OFF

VALVE

1/8 in. NPT PLUGGED TAP

GAS VALVE

.... --I, RIGHT SIDE PIPING

_(.=.__=.-,_t_(STANDARD)

118In. NPT PLUGGED

..........................j,AP

GAS VALVE

FIGURE 24

Page 15

Page 15
Image 15
Lennox International Inc G32Q3-75, G32Q3-100, G32Q5-125 j,AP, Condensate Plumbing, groundjoint type, Left Side Piping, Page