Figure 14. Unpacking the SMC - Storage Array

Figure 14. Unpacking the SMC - Storage Array

Planning and configuring your installation

Refer to “Planning your installation” on page 13 for information on overall system configuration requirements.

Refer to the Secure Managed Client (SMC) - Storage Array Setup Poster that shipped with your system for instructions on installing the processors, drives, and memory.

Rack installation prerequisites

The SMC - Storage Array is designed for installation into an industry standard 48.26-cm (19-inch) cabinet capable of holding the unit.

vMinimum depth: 70.76 cm (27.83 inches) from rack posts to maximum extremity of enclosure (excludes rear cabling).

vWeight: up to 30 kg (66.20 lb), dependent upon configuration, per enclosure.

vA minimum gap of 2.54-cm (1-inch) clearance is required between the rack cover and front of drawer. A 5.08 cm (2-inch) rear clearance between rear of drawer and rear of rack is recommended to maintain correct airflow around the enclosure.

vThe rack should present a maximum back pressure of 0.5 mm (5 pascals) water gauge.

Chapter 3. Getting Started 15