Cycle Troubleshooting Guide

1. Trouble analysis

1. Check temperature difference between intake and discharge air and operating current.

Temp. Difference

Operating Current

Temp. difference

:approx. 0°F

All amount of refrigerant leaked out.

Current

:less than 80% of

Check refrigeration cycle.

 

rated current

 

 

 

 

Refrigerant leakage

 

 

Temp. difference

:approx. 8°C(14°F)

Current

:less than 80% of

Clog of refrigeration cycle

 

rated current

Defective compressor

 

 

 

 

 

 

Temp. difference

:less than 8°C(14°F)

 

Current

:less than 80% of

Excessive amount of refrigerant

 

rated current

 

 

 

 

 

 

 

Temp. difference

:over 8°C(14°F)

Normal

 

 

 

Notice:

Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure

Temperature

 

 

(Compared with the

(Compared with the

Cause of Trouble

Description

normal value)

normal value)

 

 

 

 

 

 

 

High

Defective compressor

Current is low.

 

Defective 4-way reversing valve

Higher

 

 

 

 

 

Normal

Excessive amount of refrigerant

High pressure does not quickly

 

 

rise at the beginning of operation.

 

 

 

 

 

 

 

 

 

Insufficient amount of

Current is low.

Lower

Higher

refrigerant(Leakage)

 

 

 

Clogging

Current is low.

 

 

 

 

Notice:

1.The suction pressure is usually 4.5~5.0 kg/cm2G at normal condition.

2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.

- 42 -

Page 42
Image 42
LG Electronics LSC183VMA service manual Cycle Troubleshooting Guide, Trouble analysis