Cycle Troubleshooting Guide
1. Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Operating Current
Temp. difference | :approx. 0°F | All amount of refrigerant leaked out. | |
Current | :less than 80% of | ||
Check refrigeration cycle. | |||
| rated current | ||
|
| ||
|
| Refrigerant leakage | |
|
| ||
Temp. difference | :approx. 8°C(14°F) | ||
Current | :less than 80% of | Clog of refrigeration cycle | |
| rated current | Defective compressor | |
|
|
| |
|
|
| |
Temp. difference | :less than 8°C(14°F) |
| |
Current | :less than 80% of | Excessive amount of refrigerant | |
| rated current |
| |
|
|
| |
|
|
| |
Temp. difference | :over 8°C(14°F) | Normal | |
|
|
|
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure | Temperature |
|
| |
(Compared with the | (Compared with the | Cause of Trouble | Description | |
normal value) | normal value) |
|
| |
|
|
|
| |
| High | Defective compressor | Current is low. | |
| Defective | |||
Higher |
|
| ||
|
|
| ||
Normal | Excessive amount of refrigerant | High pressure does not quickly | ||
| ||||
| rise at the beginning of operation. | |||
|
|
| ||
|
|
|
| |
|
| Insufficient amount of | Current is low. | |
Lower | Higher | refrigerant(Leakage) |
| |
|
| Clogging | Current is low. | |
|
|
|
|
Notice:
1.The suction pressure is usually 4.5~5.0 kg/cm2G at normal condition.
2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
- 42 -