Contents
MODEL LSC183VMA
SERVICE MANUAL
Room Air Conditioner
Wiring Diagram
Contents
Dimensions
Refrigeration Cycle Diagram
Code of Model
Details of 2003 LG Model Name
Code
Type
Room temperature control
Functions
Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature
Setting the Time or Timer Timer Selection
Remote Control
Room, Temperature Checking
Temperature Setting
Product References
Dimensions
1 Indoor Unit
Indoor Unit
Gas side
2 Outdoor Unit 18K
OUTDOOR UNIT
Refrigeration Cycle Diagram
Cooling Only Models
INDOOR UNIT
2 Outdoor Unit 18K
Wiring Diagram
18K Cooling Only Models
1 Indoor Unit
Cooling Mode Operation
Operation Details
1. MAIN UNIT FUNCTION
DISPLAY
Defrost Control
Heating Mode Operation
Fuzzy Operation C/O Model
Fuzzy Operation H/P Model
1 Fuzzy Operation for Cooling
3 Fuzzy Operation for Heating
On-Timer Operation
Airflow Speed Selection
2 Fuzzy Operation for Dehumidification
Chaos Swing Mode
Off-Timer Operation
Off-Timer ↔ On-Timer Operation
Sleep Timer Operation
Test operation
Remote Control Operation Mode
Jet Cool Mode Operation H/P Model
Forced Operation
2. Cooling Model
Display Function
Self-diagnosis Function
1. Heating Model
2 Piping length and elevation
Installation
1. Installation of indoor, Outdoor unit
1 Select the best location
3. Drain hose junction
3 Preparing work for Installation
1. Open panel front
2. Cover pipe and cover side remove
5 Preparing work for installation
4 How to fix installation plate
1. Cut the pipes and the cable
2. Flaring Work and Connection of Piping
1 Flaring work
2 Connection of piping Indoor
5. Wrap the insulation material around the connecting portion
3. Indoor unit installation
For right piping. Follow the instruction below
Installation Information For right piping Good case
Bad case
3 Connection of the pipes-Outdoor
Every wire must be connected firmly
3. Connecting The Cable Between Indoor Unit and Outdoor Unit
Wiring Diagram
2. Separately wire the high and low voltage line
2 Connection method of the connecting cableExample
1. To check the drainage
4. checking the Drainage and forming the pipings
1 Checking the drainage
2 Form the piping
3 Connect the cable to the indoor unit
Air Conditioner
CAUTIONI
1. Preparation
5. Air Purging
1 Air purging
2 Air purging with vacuum pump
Soap water method
3. Evacuation
4. Finishing the job
6. Panel Front Assembly
left
3. Drive three screws
Pump Down Procedure
7. Test Running
PUMP DOWN
1. Prepare remote control
Cooling Operation Auto Operation Healthy Dehumidification Operation
Name and Function-Remote Control
Operation
Operation Mode
Disassembly of the parts Indoor unit
1. To remove the Grille from the Chassis
2. To remove the Control Box
3. To remove the Evaporator
4. Before removing the Turbo Fan
5. To remove the Motor
2-way Valve Liquid Side
2-way, 3-way Valve
1 Recheck the piping connections
Procedure
1. Air purging
CAUTION Do not leak the gas in the air during Air purging
4 Air purging of the charge hose
2. Pumping down
Procedure
2 Operate the unit for 10 to 15 minutes
7 Mount the valve stem nuts and the service port nut
1 Re-air purging
Procedure
Re-installation
2 Connect the charge set to the 3-way valve’s port
2 Balance refrigerant of the 2-way, 3-way valves
Procedure
Gas leakage
All amount of refrigerant leaked
3. Evacuation
Vacuum pump
Procedure
After Evacuation
4. Gas Charging
Procedure
5 Mount the valve stem nuts and the service port nut
1. Trouble analysis
Cycle Troubleshooting Guide
2. Product does not operate at all
Refer to Electronic Control Device drawing and Schematic diagram
3. The product is not operate with the remote controller
COMP OFF
4. Compressor/Outdoor Fan are unable to drive
Check point
COMP ON
5. When Indoor Fan does not operate
6. When Vertical Louver does not operate
7. When a comunication error occurs
8. The phenomena in case of connecting error INDOOR UNIT
On for 0.5 second
Off for 3 seconds
OUTDOOR UNIT
MODELS
9. Voltage of Connectors according to
Indoor Fan Speed
No. of pins
MODEL
Electronic Control Device
1 MAIN PWB ASSYIndoor Unit
TOP VIEW BOTTOM VIEW PWB ASSY SVC PART LIST
2 MAIN PWB ASSYOutdoor Unit
PWB ASSY SVC PART LIST
OPTIONAL FUNCTION
PWB ASM6871A20363
3 DISPLAY PWB ASSEMBLY
4 SUB P.W.B ASSEMBLY
TOP VIEW BOTTOM VIEW
1. Indoor Unit
DiagramSchematic
OUTDOOR
MICOM
2. Outdoor Unit
1. Indoor Unit
Exploded View and Replacement Parts List
REMARKS
Parts Listindoor
LOCATION
DESCRIPTION
2. Outdoor unit18K
REMARKS
Parts Listoutdoor
LOCATION
DESCRIPTION
MEMO
MEMO