TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT™ develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation.

1.The fault indicator will illuminate indicating the UPS detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional load/battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

! Fault

E

D

C

B

A

BYPASS

UPS

ON

BATTERY

AC

INPUT

Load / Battery Level Indicators

All. On bypass due to output overload (beep every half second)

A.On bypass due to over temperature condition (beep every 4 seconds)

B.On bypass due to DC bus overvoltage (beep every 4 seconds)

C.On bypass due to control power supply failure (beep every 4 seconds)

D.On bypass due to PFC failure (beep every 4 seconds)

E.On bypass due to inverter failure (beep every 4 seconds)

A&C. UPS failed battery test (long beep every minute)

C&E. UPS shutdown due to command from communication port (SNMP); no beep

The fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational.

If a problem persists consult your dealer, or contact Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.