Liebert 700-3000 VA user manual Upstation GXT Battery RUN Times, Internal Battery minutes

Models: 700-3000 VA

1 28
Download 28 pages 39.76 Kb
Page 19
Image 19

UPSTATION GXT BATTERY RUN TIMES

(Discharge times are at 25° C ambient)

Internal Battery (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

52

95

95

170

80

160

101

20%

38

46

46

128

40

83

51

30%

30

33

33

95

29

47

28

40%

23

26

26

70

21

34

20

50%

16

19

19

50

15

27

15

60%

12

14

14

37

11

21

12

70%

10

12

12

29

9

18

10

80%

8

9

9

24

7

15

8

90%

7

8

8

20

6

13

7

100%

5

7

7

18

5

11

6

Internal Battery + 1 External Battery Cabinet (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

N/A

N/A

479

554

408

343

273

20%

N/A

N/A

255

337

215

204

140

30%

N/A

N/A

150

212

125

133

78

40%

N/A

N/A

110

154

95

100

57

50%

N/A

N/A

85

116

75

77

44

60%

N/A

N/A

66

89

57

60

35

70%

N/A

N/A

56

73

48

50

30

80%

N/A

N/A

48

63

40

43

26

90%

N/A

N/A

41

53

35

36

22

100%

N/A

N/A

35

46

29

31

18

Internal Battery + 2 External Battery Cabinets (minutes)

Load%

700MT

1000MT

 

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

N/A

N/A

 

848

923

718

623

444

20%

N/A

N/A

425

507

365

345

236

30%

N/A

N/A

243

305

208

211

138

40%

N/A

N/A

196

240

164

156

100

50%

N/A

N/A

168

199

139

120

75

60%

N/A

N/A

133

156

112

94

59

70%

N/A

N/A

109

126

94

81

50

80%

N/A

N/A

89

104

78

70

43

90%

N/A

N/A

77

89

68

62

36

100%

N/A

N/A

66

77

58

54

31

19