BATTERY CABINET SPECIFICATIONS

MODEL NUMBER

GXT36VBATT

 

GXT48VBATT

 

GXT96VBATT

Used w/ UPS Model

1000RT

 

1500RT

 

2000RT/3000RT

DIMENSIONS: in (mm)

 

 

 

 

 

Unit

177 x 522 x 430

 

177 x 522 x 430

 

177 x 522 x 430

W x D x H

(7.0 x 19.3 x 16. 9)

 

(7.0 x 19.3 x 16. 9)

 

(7.0 x 19.3 x 16. 9)

Shipping

13.38 x 26.0 x 22.25

 

13.38 x 26.0 x 22.25

 

13.38 x 26.0 x 22.25

W x D x H

(340 x 660 x 565)

 

(340 x 660 x 565)

 

(340 x 660 x 565)

WEIGHT: lbs (kg)

 

 

 

 

 

Unit

61.3 (27.9)

 

71.6 (32.5)

 

71.6 (32.5)

Shipping

68.4 (31)

 

78.7 (35.7)

 

78.7 (35.7)

BATTERY PARAMETERS

 

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

# of Strings x Qty/Str. x

2x3x12Vx7.0 or 7.2 AH

 

2x4x12Vx7.0 or 7.2 AH

 

1x8x12Vx7.0 or 7.2

Batt. Voltage x Batt.

 

 

 

 

 

 

AH

Rating

 

 

 

 

 

 

 

 

 

Batt. Mfg./ Part #

CSB GP1270F2 or Panasonic LC-R127R2CH1

Back-up Time

See Typical Battery Discharge Curves

Recharge Time

5 Hours to 95% capacity after full discharge into 100% load

ENVIROMENTAL

 

 

 

 

 

Operating

+32° F to +104° F (0° C to +40° C)

Temperature

 

 

 

 

 

Storage

+5° F to +122 °F (-15° C to +50° C)

Temperature

 

 

 

 

 

Relative Humidity

 

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000 m) at 40° C without derating

Storage Elevation

50,000 ft. (15.000 m) maximum

 

AGENCY

 

 

 

 

 

Safety

UL 1778, c-UL Listed; TUV, CE LVD compliant

RFI/EMI

FCC Part 15, Subpart B, Class A; EN5022 Class B; CE ECM compliant

Immunity

IEEE 587 Category A; IEC 801-2, Level 4;

 

IEC801-3, Level 3

 

IEC801-4, Level 4

 

IEC801-5, Level 3