24
SPECIFICATIONS
MODEL NUMBER GXT1000RT-120 GXT1000RTE-120
MODEL RATING
VA/W
1000 / 700 1000 / 700
DIMENSIONS: in (mm)
Unit
Wx D x H
7.0 x 19.3 x 16.9
(177 x 522 x 430)
7.0 x 19.3 x 16.9
(177 x 522 x 430)
Shipping
Wx D x H
13.38 x 26.0 x 22.25
(340 x 660 x 565)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
WEIGHT: lbs (kg)
Unit 51.9 (23.6) 68.4 (31.1)
Shipping 59.0 (26.8) 75.5 (34.3)
INPUT AC PARAMETERS
Voltage Range (typical) 120 VAC nominal; variable based upon output load
100%- 70% Loading 80-83 VAC to 134-138 VAC
70%- 30% Loading 70-73 VAC to 134-138 VAC
30%- 0% Loading 60-62 VAC to 134-138 VAC
Frequency 48.1- 51.9 Hz or 57.6 - 62.4 Hz; auto sensing
Input Power Cord 6 ft. detached,
w/ NEMA 5-15 plug
6 ft. detached,
w/ NEMA 5-15 plug
OUTPUT AC PARAMETERS
Output Receptacles(8) NEMA 5-15R (8) NEMA 5-15R
Voltage 100/110/120/127 (switch selectable) VAC; ±3%
Frequency 50 Hz or 60Hz
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated,nonspillable, lead acid
Qty. x Voltage x Rating 3 x 12V x 7 or 7.2 AH 6 x 12V x 7 AH
Batt. Mfg./ Part # CSB GP1270F2 or Panasonic LC-R127R2CH1
Back-up Time See Typical Battery Discharge Curves
Recharge Time 5 Hours to 95% capacity after
full discharge into 100% load
10 Hours to 95% capacity after
full discharge into 100% load
ENVIROMENTAL
Operating Temperature +32° F to +104° F (0° C to +40° C)
Storage Temperature +5° F to +122 °F (-15° C to +50° C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to10,000 ft. (3000 m) at 40° C without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise <45 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Immunity IEEE 587 Category A
DISCONTINUED