TROUBLESHOOTING GUIDE

PROBLEM

 

CAUSE

 

SOLUTION

 

 

 

 

UPS fails to start

 

UPS is short circuited or

 

Ensure UPS is off. Disconnect all loads

 

when on button is

 

overloaded

 

and ensure nothing is lodged in output

 

pressed

 

 

 

sockets. Ensure loads are not defective

 

 

 

 

 

or shorted internally.

 

 

 

Internal fuse is blown,

 

Do not attempt to open or service the

 

 

 

indicating internal fault

 

UPS. Contact your dealer or LTS.

 

Battery indicator is

 

UPS not plugged in

 

UPS is operating from battery mode,

 

illuminated

 

 

 

make certain UPS is securely plugged

 

 

 

 

 

into the wall socket

 

 

 

UPS input protection has

 

UPS is operating from battery mode.

 

 

 

opened

 

Save data and close applications.

 

 

 

 

 

Replace UPS input fuse or reset input

 

 

 

 

 

breaker, then restart UPS.

 

 

 

Utility voltage out of UPS

 

UPS is operating from battery mode.

 

 

 

input range.

 

Save data and close applications.

 

 

 

 

 

Ensure utility supply voltage is within

 

 

 

 

 

acceptable limits for UPS.

 

UPS has reduced

 

Batteries not fully charged

 

Keep UPS plugged in continuously at

 

battery time

 

 

 

least 24 hours to recharge batteries

 

 

 

UPS is overloaded

 

Check load level display and reduce load

 

 

 

 

 

level

 

 

 

Batteries may not be able to

 

Replace batteries. Contact your dealer

 

 

 

hold a full charge due to age

 

or LTS for replacement battery kit

 

Fault and Bypass

 

UPS overloaded or load

 

Check load level display and remove

 

indicators and all load

 

equipment is faulty

 

non-essential loads. Recalculate load

 

level LEDs are

 

 

 

VA and reduce number of loads

 

illuminated

 

 

 

connected to UPS. Check load

 

 

 

 

 

equipment for faults.

 

Fault and Bypass

 

UPS internal fan has a

 

Ensure UPS is not overloaded,

 

indicators and

 

problem or UPS shutdown

 

ventilation openings not blocked, or room

 

diagnostic LED A are

 

due to temperature condition.

 

ambient temperature not excessive.

 

illuminated

 

Load is on bypass power

 

Wait 30 minutes to allow UPS to cool,

 

 

 

 

 

then restart UPS. IF it does not restart,

 

 

 

 

 

contact your dealer or LTS.

 

Fault and Bypass

 

UPS internal DC bus

 

UPS requires service. Contact your

 

indicators and

 

overvoltage

 

dealer or LTS.

 

diagnostic LED B are

 

 

 

 

 

illuminated

 

 

 

 

 

Fault and Bypass

 

UPS power control fault.

 

UPS requires service. Contact your

 

indicators and

 

 

 

dealer or LTS.

 

diagnostic LED C are

 

 

 

 

 

illuminated

 

 

 

 

 

Fault and Bypass

 

UPS PFC fault.

 

UPS requires service. Contact your

 

indicators and

 

 

 

dealer or LTS.

 

diagnostic LED D are

 

 

 

 

 

illuminated

 

 

 

 

 

Fault and Bypass

 

UPS inverter fault.

 

UPS requires service. Contact your

 

indicators and

 

 

 

dealer or LTS.

 

diagnostic LED E are

 

 

 

 

 

illuminated

 

 

 

 

 

Fault and Bypass

 

UPS failed the battery test.

 

Replace batteries. Contact your dealer

 

indicators and

 

 

 

or LTS.

 

diagnostic LED A & C

 

 

 

 

 

are illuminated

 

 

 

 

 

Fault and Bypass

 

UPS shutdown due to a

 

Your UPS has received a signal or

 

indicators and

 

command from the

 

command from the attached computer. If

 

diagnostic LED C & E

 

communications port(s)

 

this was inadvertent, ensure the

 

are illuminated

 

 

 

communication cable used is correct for

 

 

 

 

 

your system. For assistance, contact

 

 

 

 

 

your dealer or LTS.

 