23
SPECIFICATIONS
MODEL NUMBER GXT700MT-120 GXT1000MT-120
MODEL RATING
VA/W
700 / 490 1000 / 700
DIMENSIONS: in (mm)
Unit
Wx D x H
6.4 x 15.6 x 8.9
(162 x 430 x 225)
6.4 x 15.6 x 8.9
(162 x 430 x 225)
Shipping
Wx D x H
11.0 x 19.75 x 14.25
(280 x 502 x 362)
11.0x 19.75 x 14.25
(280 x 502 x 362)
WEIGHT: lbs (kg)
Unit 28.8 (13.1) 34.8 (15.8)
Shipping 33.0 (15.0) 39.0 (17.7)
INPUT AC PARAMETERS
Voltage Range (typical) 120 VAC nominal; variable based upon output load
100%- 70% Loading 80-83 VAC to 134-138 VAC
70%- 30% Loading 70-73 VAC to 134-138 VAC
30%- 0% Loading 60-62 VAC to 134-138 VAC
Frequency 48.1- 51.9 Hz or 57.6 - 62.4 Hz; auto sensing
Input Power Cord 6 ft. detached,
w/ NEMA 5-15 plug
6 ft. detached,
w/ NEMA 5-15 plug
OUTPUT AC PARAMETERS
Output Receptacles (4) NEMA 5-15R (4) NEMA 5-15R
Voltage 100/110/120/127 (switch selectable) VAC; ±3%
Frequency 50 Hz or 60Hz
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating 2 x 12V x7 or 7.2 AH 3 x 12V x 7 or 7.2 AH
Batt. Mfg./ Part # CSB GP1270F2 or Panasonic LC-R127R2CH1
Back-up Time See Typical Battery Discharge Curves
Recharge Time 5 Hours to 95% capacity after full discharge into 100% load
ENVIROMENTAL
Operating Temperature +32° F to +104° F (0° C to +40° C)
Storage Temperature +5° F to +122 °F (-15° C to +50° C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to10,000 ft. (3000 m) at 40° C without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise <45 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Immunity IEEE 587 Category A
DISCONTINUED
PROD U C T