Centrifugal Switch of Burner

Check for 24 VAC output from secondary of

 

Blower Motor

transformer. If voltage is present, check for 24 VAC

 

 

at pin 6 and ground on ignition control. If the burner

 

 

blower motor is running and there is no voltage at pin

 

 

6 and the ground on the ignition control, replace the

 

 

burner blower motor.

 

Ignition Control

Check for 24 VAC supply to the ignition control at pin

 

 

6 and the ground. If voltage is present, check for 24

 

 

VAC across pin #3 and ground (pilot valve). NOTE:

 

 

The Honeywell ignition control has a 30 sec. pre-

 

 

purge (Time Delay) built in. If voltage is not present,

 

 

replace electronic control package. If the pilot valve

 

 

is energized, check to see that the high voltage

 

 

igniter circuit is also energized. To check, disconnect

 

 

the igniter lead from the ignition control. Place female

 

 

terminal of igniter lead approximately 1/8" from

 

 

terminal post on ignition control. Spark should jump

 

 

the 1/8" gap. If no spark is present, replace ignition

 

 

control. NOTE: control will try for ignition for 15

 

 

seconds only.

 

No Pilot

If the ignition control is supplied with 24 VAC and the

 

 

pilot valve (internal to valve assembly) and igniter

 

 

circuits are energized, visually check for pilot flame.

 

 

This may be done by opening the small inspection

 

 

door on the end of the burner, or by opening the

 

 

main oven door and looking under the lower finger

 

 

housings on the right side of the oven. If no pilot

 

 

flame is visible, check pilot shut-off valve.

 

Pilot Shut-off Valve

Check to see that pilot shut-off valve is open (shut-off

 

 

valve is located between valve assembly and

 

 

burner).

 

Pilot Tube

Check for gas pressure at pilot tube. Disconnect pilot

 

 

tube at burner and connect manometer to pilot tube.

 

 

If no gas pressure is present, check for blockage in

 

 

pilot tube or pilot shut-off valve. If these are clear,

 

 

and there is gas supplied to the oven, replace the

 

 

gas valve.

 

Pilot Orifice

If there is gas pressure at the pilot tube, check the

 

 

pilot orifice for obstructions. Replace as needed.

 

Burner Igniter

Check the burner igniter head for any obstructions,

 

 

also check for frayed or broken wire, (spark gap .100

 

 

in. 2.5 mm). If there is visible damage, replace igniter

 

 

assembly.

Pilot flame but no

Ignition Control

If there is a pilot flame, check for 24 VAC across

main flame

 

terminals #1 and the ground (main valve). If there is

 

 

no voltage present, replace the ignition control.

 

 

NOTE: The Honeywell ignition control has a 15-sec.

 

 

lockout built in. If pilot flame is not proven, turn off

 

 

switch, wait 30 sec. and restart. If power is supplied

 

 

to terminal #1 but there is no main flame, verify that

 

 

the main valve (internal to valve assembly) has

 

 

opened. Connect a manometer to the manifold gas

 

 

pressure tap located on the back of the valve

 

 

assembly. If no gas is present, replace valve

 

 

assembly. Check for temperature control set above

 

 

300°F.

 

Main Orifice

Check for blockage of main orifice. If there is no

 

 

blockage to the main orifice, check the temperature

 

 

control.

 

Temperature Control

Check for 120 VAC across L1 and L2 on temperature

 

(Electronic)

control board.

12

Impinger I – 1400 Series Advantage Service Manual - Dom & Int’l

Page 12
Image 12
Lincoln 1400 Series service manual