Installation & Operation Manual
1 Determine unit location
Exhaust fans
Any fan or equipment which exhausts air from the boiler room may deplete the combustion air supply and/or cause a down draft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the boiler room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
Vertical DirectAire™, Horizontal DirectAire™, and Direct Vent venting systems have specific requirements for combustion air ducts from the outside which are directly connected to the unit. See the requirements for combustion air duct in the venting section.
NOTICE | Use of filters having MERV (Minimum |
Efficiency Reporting Value) ratings higher than | |
| 4 is not recommended. Higher efficiency |
| |
| air leading to either nuisance problems or |
| potential component damage if used over |
| prolonged periods of time. Filters having |
| a MERV rating of 5 to 6 may be used |
| on a limited basis during the construction |
| phase of a project provided they are replaced |
| once filter loading becomes apparent. After |
| the construction phase is completed, it is |
| recommended that the filter be changed to a |
| 4 or lower MERV disposable type filter. |
Combustion air filter
This unit has a standard air filter located at the combustion air inlet. This filter helps ensure clean air is used for the combustion process. Check this filter every month and replace when it becomes dirty. The filter size on Models 402 - 752 is 12" x 12" x 1" (30.5cm x 30.5cm x 2.5cm) and 16" x 16" x 1" (40.6cm x 40.6cm x 2.5 cm) on Models 992 - 2072. You can find these commercially available filters at any home center or HVAC supply store.
For convenience and flexibility, you can direct the combustion air inlet from either the back or right side of the unit. To arrange the combustion air inlet for side entry, follow the steps below:
1.Remove the metal panel from the unit’s side wall (see FIG.
2.Remove screws from the air filter/bracket assembly.
3.Move the filter/bracket assembly from the rear of unit to the side opening (see FIG.
4.Attach filter/bracket assembly to the unit’s side using the
5.Attach the metal panel to the rear combustion air opening to seal it off.
Figure | Figure |
Air Inlet | Rear of Unit to Side |
NOTICE
CAUTION
During construction the air filter should be checked more frequently to ensure it does not become clogged with combustion dirt and debris.
Sustained operation of an appliance with a clogged filter may result in nuisance operational problems, bad combustion, and
12