5 Electrical connections
Wiring of the cascade
When wiring the heaters for Cascade operation, select one heater as the Leader. The remaining heaters will be designated as Members. See page 50 Configuration of the Cascade for a detailed explanation of this procedure.
On boilers, connect the system supply sensor and outdoor air sensor (if used) to the Leader boiler. The location of the system supply sensor should be downstream of the boiler connections in the main system loop (FIG.’s
If outdoor air reset is desired, the outdoor air sensor should be wired to the low voltage connection board at the terminals marked for the outdoor air sensor (FIG.
If a Thermostat, Zone Control enable output, or Building Management System enable output are available, it should be wired to the low voltage connection board on the Leader boiler at the Staging S1 terminals. If the boilers are to run continuously, leave the jumper wire between these terminals. This will initiate a call for heat on the Cascade. Also, leave the jumpers on the Staging S1 terminals of all the Member heaters. This will allow them to run independently should the Leader heater fail.
Installation & Operation Manual
Figure 5-4_Low Voltage Field Wiring Connections
TO MONITORING DEVICE | 1 | ALARM |
|
| |
2 | CONTACTS |
|
| ||
|
|
| |||
TO MONITORING DEVICE | 3 |
|
| ||
4 | CONTACTS |
|
| ||
|
|
| |||
| 5 | OPEN | VALVE | ||
THREE WAY | 6 | CLOSE | |||
VALVE | 7 | COM | |||
|
| ||||
|
|
| |||
| 8 | S1 |
|
| |
| S1 | S1 |
|
| |
| 9 |
|
| ||
| 10 | S2 |
|
| |
EXTERNAL | S2 | S2 | STAGING | ||
11 | |||||
STAGING | 12 | S3 | |||
SEQUENCER | |||||
S3 | S3 | ||||
LOUVER | 13 |
|
| ||
PROVING | 14 | S4 |
|
| |
SWITCH | S4 | S4 |
|
| |
15 |
|
|
|
| 16 | LOUVER |
|
|
| 17 | PROVING SW |
|
LINE |
| 18 | LOUVER |
|
TO LOUVER |
| 19 | RELAY COIL |
|
DHW TANK |
| 20 | TANK |
|
| 21 | AQUASTAT |
| |
THERMOSTAT |
|
| CN3 |
|
|
|
|
| |
| 22 | TANK |
| |
SENSOR |
| 23 | SENSOR |
|
FROM | A | 24 | SHIELD | CASCADE |
TO NEXT |
|
| ||
PREVIOUS |
| 25 | A |
|
HEATER | B |
| ||
| A | 26 | B |
|
HEATER | B | 27 | SHIELD |
|
|
| |||
|
| 28 | + |
|
|
| 29 | - BMS IN |
|
EXTERNAL |
| 30 | + |
|
SEQUENCER/ |
| 31 | - RATE OUT |
|
BUILDING |
| 32 | SHIELD |
|
AUTOMATIC |
| MODBUS | ||
|
|
| ||
CONTROL |
| 33 | A | |
|
| |||
|
| 34 | B |
|
|
| 35 | SHIELD |
|
|
|
| CN2 |
|
On water heaters, connect the tank thermostat or BMS enable output to the low voltage connection board on the Leader heater, at the terminals marked for the tank Aquastat. If a tank sensor is used, connect this sensor to the low voltage connection board on the Leader heater, at the terminals marked for the tank sensor.
Communication between the Leader heater and the Member heaters is accomplished by using shielded,
OUTDOOR
AIR SENSOR
SYSTEM SUPPLY
SENSOR
SYSTEM RETURN
SENSOR
PUMP SPEED | |
INPUT | COMMON |
(BOILER ONLY)
OUTDOOR |
SENSOR |
SYS SUPPLY |
SENSOR |
SYS RETURN |
SENSOR |
+ |
- PUMP IN |
CN2 |
46