Wiring of the cascade

5 Electrical connections

Wiring of the cascade

When wiring the heaters for Cascade operation, select one heater as the Leader. The remaining heaters will be designated as Members. See page 50 Configuration of the Cascade for a detailed explanation of this procedure.

On boilers, connect the system supply sensor and outdoor air sensor (if used) to the Leader boiler. The location of the system supply sensor should be downstream of the boiler connections in the main system loop (FIG.’s 4-3 and 4-6). The system supply sensor should be wired to the low voltage connection board at the terminals marked for the system supply sensor (see FIG. 5-4). The Leader control will use the water temperature at the system supply sensor to control the operation of the Cascade.

If outdoor air reset is desired, the outdoor air sensor should be wired to the low voltage connection board at the terminals marked for the outdoor air sensor (FIG. 5-4). If the outdoor air sensor is connected, the Leader control will calculate the water temperature set point based on the programmed reset curve parameters. If the outdoor air sensor is not connected, the Leader control will maintain the space heating (SH) set point that is programmed into the control.

If a Thermostat, Zone Control enable output, or Building Management System enable output are available, it should be wired to the low voltage connection board on the Leader boiler at the Staging S1 terminals. If the boilers are to run continuously, leave the jumper wire between these terminals. This will initiate a call for heat on the Cascade. Also, leave the jumpers on the Staging S1 terminals of all the Member heaters. This will allow them to run independently should the Leader heater fail.

Installation & Operation Manual

Figure 5-4_Low Voltage Field Wiring Connections

TO MONITORING DEVICE

1

ALARM

 

 

2

CONTACTS

 

 

 

 

 

TO MONITORING DEVICE

3

RUN-TIME

 

 

4

CONTACTS

 

 

 

 

 

 

5

OPEN

3-WAY

VALVE

THREE WAY

6

CLOSE

VALVE

7

COM

 

 

 

 

 

 

8

S1

 

 

 

S1

S1

 

 

 

9

 

 

 

10

S2

 

 

EXTERNAL

S2

S2

STAGING

11

STAGING

12

S3

SEQUENCER

S3

S3

LOUVER

13

 

 

PROVING

14

S4

 

 

SWITCH

S4

S4

 

 

15

 

 

 

 

16

LOUVER

 

 

 

17

PROVING SW

 

LINE

 

18

LOUVER

 

TO LOUVER

 

19

RELAY COIL

 

DHW TANK

 

20

TANK

 

 

21

AQUASTAT

 

THERMOSTAT

 

 

CN3

 

 

 

 

 

10K-TANK

 

22

TANK

 

SENSOR

 

23

SENSOR

 

FROM

A

24

SHIELD

CASCADE

TO NEXT

 

 

PREVIOUS

 

25

A

 

HEATER

B

 

 

A

26

B

 

HEATER

B

27

SHIELD

 

 

 

 

 

28

+ 0-10V

 

 

 

29

- BMS IN

 

EXTERNAL

 

30

+ 0-10V

 

SEQUENCER/

 

31

- RATE OUT

 

BUILDING

 

32

SHIELD

 

AUTOMATIC

 

MODBUS

 

 

 

CONTROL

 

33

A

 

 

 

 

34

B

 

 

 

35

SHIELD

 

 

 

 

CN2

 

On water heaters, connect the tank thermostat or BMS enable output to the low voltage connection board on the Leader heater, at the terminals marked for the tank Aquastat. If a tank sensor is used, connect this sensor to the low voltage connection board on the Leader heater, at the terminals marked for the tank sensor.

Communication between the Leader heater and the Member heaters is accomplished by using shielded, 2-wire twisted pair communication cable. Connect one of the twisted pair wires to terminal A on each of the low voltage connection boards, and the other wire of the twisted pair to terminal B on each of the low voltage connection boards. Connect the shield wire to the shield ground terminal on all of the heaters. If more than two heaters are on the Cascade, daisy chain the wiring from the Cascade terminals on the second heater to the Cascade terminals on the third heater, then from the third to the forth, and so on. The connections can be made in any order, regardless of the addresses of the heaters. Try to keep each cable as short as possible.

OUTDOOR

AIR SENSOR

SYSTEM SUPPLY

SENSOR

SYSTEM RETURN

SENSOR

PUMP SPEED

0-10VDC

INPUT

COMMON

(BOILER ONLY)

OUTDOOR

SENSOR

SYS SUPPLY

SENSOR

SYS RETURN

SENSOR

+ 0-10V SYS

- PUMP IN

CN2

Figure 5-4_Low Voltage Field Wiring Connections 46 Manual background

Page 46