9 Maintenance
Maintenance and annual startup
Table 9A_Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
| ||
| • Address reported problems | |||
| • Inspect | interior; clean and vacuum if | ||
|
| necessary; | ||
| • Check | for leaks (water, gas, flue, | ||
|
| condensate) | ||
| • Examine venting system | |||
UP- | • Check system water pressure/system | |||
| piping/expansion tank | |||
START |
| |||
• | Check control settings | |||
| ||||
| • | Check igniter | ||
ANNUAL | • Check wiring and connections | |||
• Check flue gas passageways | ||||
| ||||
| • | Flame inspection (stable, uniform) | ||
| • Inspect and clean the burner | |||
| • Check manifold gas pressure | |||
| • Perform | |||
|
| performance verification per Section 6 in | ||
|
| the | ||
|
| Operation Manual. |
If combustion or performance indicate need:
•Clean heat exchanger with a stiff bristle brush
•Remove and clean burners using water. Dry before
•Clean the blower wheel with a brush and vacuum. Do not let dirt from cleaning get pulled into the blower.
Owner maintenance
(see the
instructions)
| • Check appliance area |
| • Check pressure/temperature |
Daily | gauge |
|
| • Check vent piping |
| • Check air piping |
Monthly | • Check relief valve |
| |
| • Replace combustion air filter |
| Note: More frequent replacement may |
| be necessary in dirty environments. |
|
|
Periodically | • Test low water cutoff (if used) |
| • Reset button (low water cutoff) |
|
|
Every | • Check appliance piping (gas and |
water) for leaks | |
6 months | • Operate relief valve |
| |
|
|
End | • Shut appliance down (unless |
boiler used for domestic hot | |
of season | water) |
months |
|