Lochinvar 402 - 2072 B, 8_VerticalDirectAire Installation, w/Rooftop Combustion Air Inlet, Model

Models: 402 - 2072

1 80
Download 80 pages 43.41 Kb
Page 21
Image 21
Figure 2-8_Vertical DirectAire™ Installation

Installation & Operation Manual

2 Venting (continued)

￿WARNING Only use a sidewall air inlet cap supplied by the appliance manufacturer or a rooftop air inlet cap supplied by either the vent

3'

or appliance manufacturer. Using any other air inlet cap for single

MIN

 

unit installations or using a common air inlet cap for multiple

12"

units with insufficient free area and/or protections from wind and

weather may result in operational problems and the spillage of

MIN

 

flue products. Spillage of flue products can cause personal injury

 

or death due to carbon monoxide poisoning.

 

For single unit installations with sidewall air inlet you must order the sidewall air

 

inlet kit from the appliance manufacturer. The part number for each SVK kit is

 

listed by unit size in Table 2B.

For single unit installations with rooftop air inlet (see FIG. 2-8), you must order the rooftop air inlet kit from the appliance manufacturer. The part number for each VDK kit is listed by unit size in Table 2B. Purchase the flue pipe, rooftop flue termination, and air inlet pipe locally.

Figure 2-8_Vertical DirectAire™ Installation

There is no vent kit for combined air supply systems for multiple units. Make

w/Rooftop Combustion Air Inlet

sure the air inlet cap is properly sized. You must purchase this cap locally.

Venting of flue products

For venting flue products vertically to the outdoors, follow all requirements in the installation instructions for conventional venting in this manual.

Follow all clearance requirements in Vertical Vent Termination Clearances and

Location on page 17.

A barometric damper is not required in the flue on Vertical DirectAire™ installations if the draft is within the negative 0.02 to 0.08 inches w.c. required for proper operation. If the draft exceeds this range, install a barometric damper.

TABLE - 2B

DIRECTAIRE KITS

MODEL

HORIZONTAL KIT*

VERTICAL KIT*

402

SVK3047

VDK3026

502

SVK3047

VDK3026

652

SVK3048

VDK3027

752

SVK3048

VDK3027

992

SVK3040

VDK3023

1262

SVK3041

VDK3024

1442

SVK3041

VDK3024

1802

SVK3041

VDK3024

2072

SVK3041

VDK3024

*The SVK kits include a DV box adapter and sidewall air inlet cap. The VDK kits include a DV box adapter and a rooftop air inlet cap.

w/Rooftop Combustion Air Inlet 21 Venting of flue products