Installation & Operation Manual
9 Maintenance
Perform start-up and checks
1.Start appliance and perform checks and tests specified in Section 7 -
2.Verify cold fill pressure is correct and that operating pressure does not go too high.
Check burner flame
Visually check main burner flames at each
WARNING The area around the burner viewport is hot and direct contact could result in burns.
Figure 9-2_Flame Pattern Illustration
Check flue gas passageways
Any sign of soot around the inner jacket, outer jacket, flue pipe connections, burner or in the areas between the fins on the copper heat exchanger indicates a need for cleaning. The following cleaning procedure must only be performed by a qualified serviceman or installer. Proper service is required to maintain safe operation. Properly installed and adjusted units seldom need flue cleaning.
NOTICE | All gaskets/sealants on disassembled | |
components or jacket panels must be replaced | ||
| ||
| with new gaskets/sealants on reassembly. | |
| Gasket and sealant kits are available from | |
| your distributor. |
CAUTION When a Category IV vent system is disconnected for any reason, the flue must
be reassembled and resealed according to the vent manufacturer’s instructions.
NORMAL
YELLOW FLAME
YELLOW TIP
FLAME LIFT
Inspect and clean burner
1. | Turn off main power to unit. |
2. | Turn off main manual gas shutoff to unit. |
3. | Remove the front outer jacket panels. |
4. | Disconnect manifold from gas train using union(s) just |
| below each gas valve(s). |
5. | Remove mounting screws from manifold mounting |
Normal Flame: A normal flame at 100% of burner input is blue, with slight yellow tips, a well defined flame and no flame lifting.
Yellow Tip: Yellow tipping can be caused by blockage or partial obstruction of air flow to the burner.
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner or excessive gas input. This condition MUST be corrected immediately.
Lifting Flames: Lifting flames can be caused by over firing the burner, excessive primary air or high draft.
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
| brackets. Pull the manifold/orifice assembly away from |
| burners. Repeat for each manifold assembly. |
6. | Remove two mounting screws from burner and slide |
| burner out toward front of unit. Use caution to prevent |
| damage to burners, refractory, hot surface igniter or wiring. |
7. | Remove soot from burners with a stiff bristle brush. |
| Dirt may be removed from burner ports by rinsing the |
| burner thoroughly with water. Drain and dry burners |
| before |
When installed in a dusty and dirty location, the burners may require cleaning on a 3 to 6 month schedule or as needed, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non combustible particulate matter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause
74