Installation & Operation Manual
7 Operating information
Status display screens
Status Display Screens
By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
Screen # | Display Shows | Description |
| HTR: OFF | The unit has been turned OFF by the Enter/Reset button on the |
| SMART SYSTEM display panel. | |
|
| |
|
|
|
| HTR: | The unit has not received a call for heat from a remote thermostat nor |
| has it received a call for heat from a DHW thermostat. | |
|
| |
|
|
|
|
| The unit has met the water temperature set point, but is still receiving |
| HTR: SETPOINT MET | a call for heat from either a remote thermostat, a DHW thermostat, |
|
| or a BMS. |
|
|
|
| HTR: | The unit has initiated the 10 second air purge upon a call for heat. |
Screen #1 |
|
|
| The unit has begun the 30 second heatup time prior to the trial for | |
Line 1 | HTR: IGNITER * ON | ignition. Display will show IGNITER A or IGNITER B depending on |
|
| which stage has priority. |
|
|
|
| HTR: RUN STG **** | The unit has fired and is running at the displayed number of stages |
| Or | |
| (1,2,3,4) | |
| HTR: DHW STG **** | |
|
| |
|
|
|
|
| The call for heat has been satisfied and the unit runs the fan for an |
| HTR: | additional 10 seconds to clear the combustion chamber and vent |
|
| system of residual flue products. |
|
|
|
| HTR: SERVICE MODE | The unit has been placed in a temporary mode that will allow the unit |
| to fire for the purpose of combustion analysis. | |
|
| |
|
|
|
|
| When the outlet sensor has been selected as the control sensor |
| OUT: ***F (***) | (default), the control will display the outlet temperature as well as the |
|
| set point in parenthesis. |
|
|
|
Screen #1 |
| If the outlet sensor has not been selected as the control sensor or a |
OUT: ***F | system supply sensor is connected, only the outlet temperature will be | |
Line 2 |
| displayed. |
|
|
|
| OUT: OPEN | The control does not detect the outlet sensor. |
|
|
|
| OUT: SHORTED | The outlet sensor wires or the sensor itself has become shorted. |
|
|
|
Press the Next arrow key on the SMART SYSTEM display to access Screen #2.
58