Vertical Vent Termination Clearances

Installation & Service Manual

2Venting (continued)

Vertical Vent Termination Clearances

10' OR LESS

10' OR LESS

10' OR LESS

CHIMNEY

 

 

2' MIN

2' MIN

3' MIN

2' MIN

3' MIN

RIDGE

 

CHIMMEY WALL OR

CHIMMEY

 

PARAPET

 

Figure 2-2_Vent Termination from Peaked Roof 10' or

Figure 2-4_Vent Termination from Flat Roof 10' or Less

Less from Ridge

from Parapet Wall

 

 

 

10' OR MORE

MORE THAN 10'

 

 

10'

 

3'

 

 

2' MIN

CHIMNEY

 

RIDGE

 

 

 

3' MIN

 

 

 

NOTE:

 

 

NO HEIGHT ABOVE

 

 

PARAPET REQUIRED

 

 

WHEN DISTANCE

 

 

FROM WALLS OR

 

 

PARAPETS IS MORE

 

 

THAN 10'.

 

WALL OR

CHIMNEY

 

PARAPET

 

 

Figure 2-3_Vent Termination from Peaked Roof More

Figure 2-5_Vent Termination from Flat Roof More Than

10' from Parapet Wall

than 10' from Ridge

 

The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination. The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.

A vertical terminal less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.

The vent cap should have a minimum clearance of 4 feet (1.22m) horizontally from and in no case above or below, unless a 4 foot (1.22m) horizontal distance is maintained from electric meters, gas meters, regulators and relief equipment.

The venting system shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).

The venting system shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building.

Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30cm) above grade.

To avoid a blocked vent condition, keep the vent cap clear of snow, ice, leaves, debris, etc.

Flue gases will form a white plume in winter. Plume could obstruct window view.

Flue gas condensate can freeze on exterior surfaces or on the vent cap. Frozen condensate on the vent cap can result in a blocked vent condition. Flue gas condensate can cause discoloration of exterior building surfaces. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.

NOTICE

Examine the venting system at least once a

year. Check all joints and vent pipe

 

 

 

connections for tightness. Also check for

 

corrosion or deterioration. Immediately

 

correct any problems observed in the

 

venting system.

 