Installation & Service Manual

3Gas connections (continued)

Checking Gas Supply Pressure

GAS SUPPLY PRESSURE

MANOMETER

GAS VALVE

Figure 3-4_Gas Supply Pressure

1.

Turn the power “OFF” at the main disconnect

 

switch.

2.

Turn gas valve control knob to the “OFF” position.

3.

Shut off gas supply at the manual valve in the gas piping

 

to the appliance. If fuel supply is L.P. gas, shut off gas

 

supply at the tank.

4.

Remove the 1/8" hex plug, located on the “inlet” side of

 

the gas valve and install a fitting suitable to connect to a

 

manometer or magnahelic gauge. Range of scale should

 

be 14" w.c. or greater to check inlet pressure. See

 

FIG.’s 3-3 and 3-4 for location.

8.Set the thermostat(s) to call for heat.

9.Observe the gas supply pressure with all burners firing. Ensure inlet pressure is within specified range. Check gas supply pressure with all other gas fired appliances in operation to ensure proper gas volume during periods of peak gas usage.

10.If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agency to determine necessary steps to provide proper gas pressure to the control.

11.If the gas supply pressure is within the specified range, proceed with the following steps to return the appliance to service.

12.Turn the power “OFF” at the main disconnect switch.

13.Turn gas valve control knob to “OFF” position.

14.Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. Gas, shut off gas supply at the tank.

15.Remove the manometer and related fittings from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve.

16.Turn on gas supply at the manual valve, turn on L.P. Gas at tank if required.

17.Turn the power “ON” at the main disconnect switch.

18.Turn the gas valve control knob to the “ON” position. Spark ignition models will automatically light the pilot on a call for heat.

19.Set the thermostat to call for heat. The appliance is now ready to operate.

5.

Turn on gas supply at the manual valve, turn on L.P. gas

 

at tank if required.

6.

Turn the power “ON” at the main disconnect switch.

7.

Follow the “Lighting Instructions” in Section 6 - Startup

 

to light the pilot . Turn gas valve control knob to the

 

“ON” position.

IMPORTANT

Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Immediately repair any leak found in the gas train or related components. Do Not operate an appliance with a leak in the gas train, valves or related piping.

Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see the “Maintenance Section - Normal Flame Pattern”. Turn system off and allow burners to cool, then cycle burners again to ensure proper ignition and flame characteristics.

21

Page 21
Image 21
Lochinvar 45, 000 Btu/hr, 000 - 260 service manual Checking Gas Supply Pressure, 4Gas Supply Pressure

000 - 260, 000 Btu/hr, 45 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.