6Start-up(continued)

Operating Instructions

1.STOP! Read the safety information first.

2.Remove the control panel door.

3.Set the thermostat to the lowest setting (OFF).

4.Turn off all electrical power to the appliance.

5.This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.

6a. 45,000 - 135,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the “OFF” position.

6b. 180,000 - 260,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position.

7.Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the “What To Do If You Smell Gas” section in the safety information on page 40. If you do not smell gas go on to the next step.

8a. 45,000 - 135,000 Btu/hr models, rotate the gas control knob on the gas valve counterclockwise to the “ON” position.

8b. 180,000 - 260,000 Btu/hr models, rotate the gas control knob on the gas valve counterclockwise to the line on the collar around the knob. Allow the knob to “pop” up, and continue rotation to the “ON” position.

9.Turn on all electric power to the appliance.

10.Set the thermostat to the desired setting.

11.Re-install the control panel door.

12.If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.

Installation & Service Manual

To Turn Off Gas to Appliance

1.Set the thermostat to the OFF position.

2.Turn off all electric power to the appliance if service is to be performed.

3a. 45,000 - 135,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the “OFF” position. Do not force.

3b. 180,000 - 260,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position. Do not force.

Should overheating occur or the gas fail to WARNING shut off, turn off the external manual gas

valve to the appliance.

Safety Shutoff Test for Spark Ignition Pilot System

1.Turn “OFF” gas supply to the appliance.

2.Turn thermostat to highest setting.

3.Turn electric power “ON”.

4.Pump relay pulls in to start pump.

5.The ignition will begin sparking at the pilot.

6.The ignition module will lock out after the 90 second trial for ignition period.

7.Immediately call a qualified serviceman or installer to repair an ignition system that fails to lock out and properly shut down burner operation.

8.After successful completion of the test, readjust the thermostat to normal setting.

9.Turn “ON” gas supply.

10.Turn power “OFF” then “ON” to reset ignition module.

11.If ignition system fails to operate properly, repair work must be performed by a qualified serviceman or installer.

41

Page 41
Image 41
Lochinvar 000 - 260, 45, 000 Btu/hr Operating Instructions, Safety Shutoff Test for Spark Ignition Pilot System

000 - 260, 000 Btu/hr, 45 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.