Inspection of Heat Exchanger Waterways

Installation & Service Manual

7Maintenance

s.Ensure that all burner ports are cleaned to remove any soot. See Inspection and Cleaning Procedure, page 47.

t.Carefully re-install the heat exchanger, “V” baffles, jacket panels, and wires.

u.Reassemble all gas and water piping. Test for gas leaks.

v.Cycle the appliance and check for proper operation.

Inspection of Heat Exchanger Waterways

Appliances operated in hard water areas should have periodic inspections of the tubes to be sure that no sediment or scale accumulates on the heat transfer surfaces. Inspection plugs are located at both ends of the heat exchanger. Inspection plugs should be removed and tubes inspected at the end of the first 45 days of operation and again at the end of 90 days of operation. If no scale accumulation is observed, inspections can be made at the end of each six months of operation.

OUTER AIR

DEFLECTOR

UPPER FRONT

JACKET PANEL

Gas Train and Controls FLAME ROLL-OUT SWITCH /

DETAIL A INTERLOCK SWITCH

IMPORTANT

Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Immediately repair any leak found in the gas train or related components. Do Not operate an appliance with a leak in the gas train, valves or related piping.

LOWER FRONT

JACKET PANEL

HEX FILLER BRACKET

Gas Train and Controls

Figure 7-2_Outer Air Deflector and HEX Filler Bracket

Water Circulating Pump

Inspect pump every 6 months and oil if required. Use SAE 30 non-detergent oil or lubricant specified by pump manufacturer.

Clear Area

1.Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.

2.Check frequently to be sure the flow of combustion and ventilation air to the boiler is not obstructed.

GAS FLOW

Figure 7-3_Gas Train

Review with owner

1.Review the User’s Information Manual with the owner.

2.Emphasize the need to perform the maintenance schedule specified in the User’s Information Manual (and in this manual as well).

3.Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.

4.Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.