Lochinvar CP-5M-4/08, 45, RSB-i&s-05 warranty Temperature Adjustment, Temperature Control Settings

Models: 000 Btu/hr 000 - 500 RSB-i&s-05 45 CP-5M-4/08

1 52
Download 52 pages 3.75 Kb
Page 20
Image 20
Temperature Control Settings

Temperature Control Settings

There are three setting knobs on the temperature control unless your unit is specified as a boiler only with an outdoor air reset option. If your unit is a boiler only with an outdoor air reset option, there are additional controls for this option. They are explained under Outdoor Air Reset Option, page 22.

The three setting knobs on the temperature control are for Set point, Differential, and High-Fire Offset (see Figure 28).

FIG. 26 Intermittent Pilot System F9/M9 Control Panel

FIG. 27 Control Panel Assembly 500,000 Btu/hr

TEMPERATURE ADJUSTMENT

Operating Temperature Control

NOTE:

The temperature controller is pre-set at the factory with test settings. You may need to adjust the settings to meet your specific needs.

￿WARNING

Return water temperatures must not be less than 140°F. If lower return water temperatures are required, follow the instructions for Low Temperature Bypass Requirements or Three-Way Valves, see page 35.

Locating Temperature Control

Remove the control panel door on the front of the unit in order to locate and access the temperature control.

FIG. 28 Temperature Control

Maximum Set Point Determination

The maximum set point for the control is factory set. Boilers can be set to 240°F max., water heaters are set to 190°F max., and specialty state and local codes to 200°F.

These maximum set points are established by cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller. The maximum set point is determined as shown below in TABLE-K.

TABLE K

Maximum Set point Determination

 

 

Max.

OJ1

OJ2

Set Point

Connected

Connected

240°F

Cut

Connected

190°F

Connected

Cut

200°F

Cut

Cut

160°F

NOTE:

Anytime that OJ1 is the only jumper cut, a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 190°F.

Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.

20

Page 20
Image 20
Lochinvar CP-5M-4/08, 45, RSB-i&s-05 Temperature Adjustment, Temperature Control Settings, Operating Temperature Control