with no duct, provide two permanent openings:

FIG. 5 Combustion Air Direct from Outside

FIG. 7 Combustion Air from Interior Space

1. If air is taken directly from outside the building

3. If air is taken from another interior space that is

with no duct, provide two permanent openings:

adequately ventilated, each of the two openings

 

specified above should have a net free area of one

a. Combustion air opening, with a minimum free

square inch for each 1000 Btu/hr (22cm2 per kW)

area of one square inch per 4000 Btu/hr input

of input, but not less than 100 square inches

(5.5cm2 per kW). This opening must be located

(645cm2).

within 12" (30cm) of the floor.

 

b.Ventilation air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5cm2 per kW). This opening must be located within 12" (30cm) of the ceiling.

FIG. 6 Combustion Air Through Ducts

2.If combustion and ventilation air is taken from

the outdoors using a duct to deliver the air to the room where the appliance is installed, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11cm2 per kW).

FIG. 8 Combustion Air from Outside Single Opening

4.If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7cm2 per kW). This opening must be located within 12" (30cm) of the ceiling.