CLEARANCE FROM

CLEARANCE FROM

COMBUSTIBLE CONSTRUCTION

Clearances from Combustible Construction:

Right Side - 6" Rear - 6"

Left Side - 18" (24" suggested for service) Front - 18" (24" suggested for service) Top - (measured from the top of the unit)

45,000 - 180,000 Btu/hr Models - 14"

199,999 - 500,000 Btu/hr Models - 29"

All units have been approved for alcove installation (an ALCOVE is a closet enclosure without a front door).

The boiler must not be installed on carpeting.

All units have been approved for use on combustible surfaces.

Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the appliance.

 

14"

6"

6"

 

 

18"

 

18"

FIG. 3 Clearances Models 45,000 - 180,000 Btu/hr

29"

6"

6"

18"

18"

FIG. 4 Clearances Models 199,999 - 500,000 Btu/hr

COMBUSTION AND VENTILATION AIR

REQUIREMENTS FOR

CONVENTIONALLY VENTED

APPLIANCES

Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.

The room where the appliance is installed MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.

4