3.Set the thermostat to the lowest setting (OFF).

3.Set the thermostat to the lowest setting (OFF).

4. Turn off all electrical power to the appliance.

5. Turn the gas control knob on the gas valve clockwise to the “OFF” position.

FIG. 35 Lighting Wand

FIG. 33 F1 Gas Valve 90,000 - 270,000 Btu/hr Models

6.Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the“What To Do If You Smell Gas” section in the safety information on page 24. If you do not smell gas go on to the next step.

7.Remove the lower panel door to gain access to the pilot.

8.Find the pilot - Follow the metal tube from the gas valve to the pilot. The pilot is located on the right side of the burner approximately centered in the burner tray.

FIG. 34 Pilot Location

9.Turn the control knob on the gas valve counterclockwise to the “PILOT” position.

NOTE:

The information package shipped with the appliance contains a wire lighting wand. The loop end of the wand will hold a match. The wand extends your reach to the pilot and makes lighting the pilot easier.

10.Use the loop end of the wire lighting wand, shipped with the instruction package, to hold the match and reach the pilot. An access slot is provided in the lower front jacket panel, beside the burner, to insert the lighting wand and match to the pilot. Lift the pilot cover (FIG. 35) to access the pilot. Push down and hold in the red button on the gas valve. This should start gas flow to the pilot. Continue to hold the red button in for about one (1) minute after the pilot is lit. Release the button and it will pop back up. The pilot should remain lit. If the pilot goes out, repeat steps 5 through 10.

If the red button does not pop up when released, stop and immediately call your gas supplier.

If the pilot will not stay lit after several tries, turn the gas control to “OFF” and call your service technician or gas supplier.

11.Turn the gas control knob on the gas valve counterclockwise to the “ON” position.

12.Turn on all electric power to the appliance.

13.Re-install the lower panel door.

14.Set the thermostat to the desired setting.

15.Re-install the control panel door.