OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

 

TO TURN OFF GAS TO APPLIANCE

 

 

 

1.STOP! Read the safety information first.

2.Remove the control panel door.

3.Set the thermostat to the lowest setting (OFF).

4.Turn off all electrical power to the appliance.

5.This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.

6a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the “OFF” position.

6b. 180,000 - 360,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position.

7.Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the “What To Do If You Smell Gas” section in the safety information on page 26. If you do not smell gas go on to the next step.

8a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr models, rotate the gas control knob on the gas valve counterclockwise to the “ON” position.

8b. 180,000 - 360,000 Btu/hr models, rotate the gas control knob on the gas valve counter- clockwise to the line on the collar around the knob. Allow the knob to “pop” up, and continue rotation to the “ON” position.

9.Turn on all electric power to the appliance.

10.Set the thermostat to the desired setting.

11.Re-install the control panel door.

12.If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.

1.Set the thermostat to the OFF position.

2.Turn off all electric power to the appliance if service is to be performed.

3a. 45,000 - 135,000 and 399,999 - 500,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the “OFF” position. Do not force.

3b. 180,000 - 360,000 Btu/hr models, rotate the gas control knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position. Do not force.

￿WARNING

Should overheating occur or the gas fail to shut off, turn off the external manual gas valve to the appliance.

SAFETY SHUTOFF TEST FOR SPARK

IGNITION PILOT SYSTEM

1.Turn “OFF” gas supply to the appliance.

2.Turn thermostat to highest setting.

3.Turn electric power “ON”.

4.Pump relay pulls in to start pump.

5.The ignition will begin sparking at the pilot.

6.The ignition module will lock out after the 90 second trial for ignition period on the 45,000 thru 399,999 Btu/hr models and after the 15 second trial for ignition period on the 500,000 Btu/hr model.

7.Immediately call a qualified serviceman or installer to repair an ignition system that fails to lock out and properly shut down burner operation.

8.After successful completion of the test, readjust the thermostat to normal setting.

9.Turn “ON” gas supply.

10.Turn power “OFF” then “ON” to reset ignition module.