8-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
OPERATION INDICATOR | Lighted |
Blinking
|
| Not lighted |
|
|
|
| |
No. | Abnormal | Operation indicator lamp | Symptom | Condition | Correspondence | ||
point | |||||||
|
|
|
|
|
| ||
|
| Left lamp flashes. |
|
|
|
| |
| Miswiring |
|
| • Refer to | "How to check | ||
|
|
| The serial signal from the outdoor unit is not | ||||
1 | or serial |
|
| miswiring and serial signal er- | |||
|
| received for 6 minutes. | |||||
| signal |
| ror". |
| |||
|
|
|
| ||||
|
|
|
|
|
| ||
| Indoor coil | Left lamp flashes. |
|
|
|
| |
|
|
| • Refer to | ||||
| thermistor |
|
| ||||
|
|
| The indoor coil or the room temperature ther- | ||||
2 |
|
|
| of indoor coil thermistor, and | |||
Room tem- |
|
| mistor is short or open circuit. | the room temperature thermis- | |||
|
|
| |||||
| perature |
|
| tor. |
| ||
| thermistor |
|
|
|
|
| |
|
| Left lamp flashes. |
|
|
|
| |
|
|
|
|
|
| ||
3 | Indoor fan |
|
| The rotational frequency feedback signal is | • Refer to | "Check of in- | |
motor |
|
| not emitted during the indoor fan operation. | door fan motor". | |||
|
| ||||||
|
|
|
|
|
| ||
|
| Left lamp flashes. |
|
|
|
| |
|
|
| It cannot properly read data in the nonvolatile |
|
| ||
4 | Indoor con- |
|
| • Replace the indoor electronic | |||
|
| memory of the indoor electronic control P.C. | |||||
trol system |
|
| control P.C. board. | ||||
|
| board. | |||||
|
|
|
|
| |||
|
| Indoor unit and |
|
|
| ||
|
|
|
|
|
| ||
|
| Left lamp flashes. | outdoor unit do |
|
|
| |
|
| not operate. |
| • Refer to "How to check of in- | |||
|
|
| It consecutively occurs 3 times that the com- | ||||
| Outdoor |
|
| verter/compressor". | |||
|
|
| pressor stops for overcurrent protection or | ||||
5 | power sys- |
|
| Refer to outdoor unit service | |||
|
| ||||||
| tem |
|
| manual |
| ||
|
|
| |||||
|
|
| • Check the stop valve. | ||||
|
| Left lamp flashes. |
|
|
|
| |
| Outdoor |
| The outdoor thermistors short or open circuit | • Refer to "Check of outdoor | |||
6 |
|
| thermistor". |
| |||
thermistors |
|
| during the compressor operation. | Refer to outdoor unit service | |||
|
|
|
| manual. |
| ||
|
| Left lamp flashes. |
|
| • Replace the inverter P.C. board | ||
| Outdoor |
| It cannot properly read data in the nonvolatile | ||||
7 |
|
| or the outdoor electronic con- | ||||
control sys- |
|
| memory of the inverter P.C. board or the out- | trol P.C. board. | |||
| tem |
| door electronic control P.C. board. | Refer to outdoor unit service | |||
|
|
|
| manual. |
| ||
|
| Left lamp flashes. |
|
|
|
| |
| Other ab- |
| An abnormality other than above mentioned | • Check the stop valve. | |||
8 |
|
| • Confirm the abnormality in | ||||
normality |
|
| is detected. | detail using the failure mode | |||
|
|
|
| recall function for outdoor unit. | |||
|
|
|
|
|
| ||
| Outdoor |
|
|
|
|
| |
| control |
| Outdoor unit | It cannot properly read data in the nonvolatile | • Check the blinking pattern of | ||
| system |
| |||||
|
| the LED on the inverter P.C. | |||||
9 |
| Left lamp lights up | does not oper- memory of the inverter P.C. board or the out- | ||||
board or the outdoor electronic | |||||||
| /15/17 |
| ate | door electronic control P.C. board. | control P.C. board. | ||
|
|
|
|
|
|
|
16