OPERATION INDICATOR
No. | Abnormal |
|
| Operation indicator lamp | Symptom | Condition | Correspondence | ||||||
point |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Left lamp lights and lower lamp flashes. |
|
|
| ||||||||
| MXZ type | Lower lamp flashes. | Outdoor unit | The operation mode of the each indoor unit |
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| is differently set to COOL (includes DRY) and | • Unify the operation mode. | ||
| Operation |
|
|
|
|
|
|
|
|
| operates but | ||
1 |
|
|
|
|
|
|
|
|
| HEAT at the same time, the operation mode | Refer to outdoor unit service | ||
| mode | indoor unit does | of the indoor unit that has operated at first has | manual. | |||||||||
| setting |
|
|
|
|
|
|
|
|
| not operate. | the priority. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8-5. TROUBLE CRITERION OF MAIN PARTS
Part name | Check method and criterion | Figure |
| |
Room temperature | Measure the resistance with a tester. |
|
|
|
thermistor(RT11) |
|
|
| |
Indoor coil thermistor | Refer to |
|
| |
"Indoor electronic control P.C. board", the chart of thermistor.. |
|
| ||
(RT12(MAIN),RT13(SUB)) |
|
|
|
|
Indoor fan motor(MF) | Check |
|
|
|
| Measure the resistance between the terminals with a tester. | RED |
| |
Horizontal vane | (Part temperature 50 ~ 86°F) |
|
| |
| ROTOR | |||
motor(MV) | Color of the lead wire | Normal | YLW |
|
235 ~ 255 Ω | BRN |
| ||
ORN | GRN | |||
|
|
| ||
Horizontal vane | Measure the resistance between the terminals with a tester. | RED |
| |
(Part temperature 50 ~ 86°F) |
|
| ||
motor(MV1) |
| ROTOR | ||
Vertical vane | Color of the lead wire | Normal | YLW |
|
motor(MV2) | 282 ~ 306 Ω | BRN |
| |
ORN | GRN | |||
|
| |||
|
|
|
|
17