2. Installation

2.6 Required protective devices and cable cross-sections

Recommended upstream protection

UPS power rating

Upstream circuit breaker

 

 

4000 RT

D curve - 32A

 

 

5000 RT

D curve - 32A

 

 

2 poles circuit breaker

The indicated protection ensures discrimination for each output circuit downstream of the UPS.

If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.

L

N To UPS Normal AC source

G N L

Recommended downstream protection

UPS power rating

Downstream circuit breaker

 

 

4000 RT

Z curve - 10A

 

 

 

C curve - 4A

 

 

5000 RT

Z curve - 10A

 

 

 

C curve - 6A

 

 

The indicated protection ensures discrimination for each output circuit downstream of the UPS.

If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.

Required cable cross-sections

Terminal-block cable capacity: 6 mm2, solid or stranded wire (maximum 8 mm2 or AWG 8).

Capacity for earthing conductor: 6 mm2, solid or stranded wire (maximum 8 mm2 or AWG 8).