2. Installation
2.6 Required protective devices and cable cross-sections
Recommended upstream protection
UPS power rating | Upstream circuit breaker |
|
|
4000 RT | D curve - 32A |
|
|
5000 RT | D curve - 32A |
|
|
2 poles circuit breaker
The indicated protection ensures discrimination for each output circuit downstream of the UPS.
If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.
L
N To UPS Normal AC source
G N L
Recommended downstream protection
UPS power rating | Downstream circuit breaker |
|
|
4000 RT | Z curve - 10A |
|
|
| C curve - 4A |
|
|
5000 RT | Z curve - 10A |
|
|
| C curve - 6A |
|
|
The indicated protection ensures discrimination for each output circuit downstream of the UPS.
If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.
Required cable cross-sections
◗
◗Capacity for earthing conductor: 6 mm2, solid or stranded wire (maximum 8 mm2 or AWG 8).