5. Troubleshooting |
|
| |
5.1 Troubleshooting LEDS (21) and (22) |
| ||
20 | 21 | If LED (21) is ON: | |
the equipments are protected by the UPS | |||
|
| ||
|
| but the operation is downgraded. | |
| 22 | If LED (22) is ON: | |
| the equipments are no longer protected | ||
|
| ||
|
| by the UPS. | |
|
| Press the escape button (24) to stop the | |
LOAD PROTECTED |
| audible alarm. | |
|
| ||
x.xkVA / xxx% LOADED |
|
| |
ENVIRONMENT FAULT |
| Note : | |
SINGLE UPS | 24 | ||
In case of "MULTIPLE FAULT", press the | |||
| |||
ESC |
| "Enter" button (27) and the scroll button (25) | |
25 | to get access to further details. | ||
| |||
| 27 | In case of "LCM WARNING", refer to LCM | |
| section (see section 6). | ||
|
|
5.2 Troubleshooting not requiring MGE UPS SYSTEMS
LOAD PROTECTED |
x.xkVA / xxx% LOADED |
x x x x x x x x FAULT |
SINGLE UPS |
ESC |
Press the "Enter" button (27) to display the details below : |
| |
|
|
|
Displayed details | Signification | Correction |
|
|
|
NO BATTERY | The battery is incorrectly connected | Check battery connections |
|
|
|
I/O BAD CONNECTION | AC source is not connected to the correct | Check AC wiring |
| terminals |
|
|
|
|
NO POWER MODULE | The power | Check power |
|
| section 7.1) |
|
|
|
NO BATTERY MODULE | The battery | Check battery connections (see section 7.2) |
| connected |
|
|
|
|
INV THERM OVERLOAD | The UPS shuts down automatically because | Check the power drawn by the connected |
| of a major overload. | devices and disconnect any |
|
| devices. |
|
|
|
INVERT LIMITATION | Short circuit conditions on output devices | Check the installation at the UPS output |
|
| (wiring, fault equipment) |
|
|
|