5. Troubleshooting

 

 

5.1 Troubleshooting LEDS (21) and (22)

 

20

21

If LED (21) is ON:

the equipments are protected by the UPS

 

 

 

 

but the operation is downgraded.

 

22

If LED (22) is ON:

 

the equipments are no longer protected

 

 

 

 

by the UPS.

 

 

Press the escape button (24) to stop the

LOAD PROTECTED

 

audible alarm.

 

 

x.xkVA / xxx% LOADED

 

 

ENVIRONMENT FAULT

 

Note :

SINGLE UPS

24

In case of "MULTIPLE FAULT", press the

 

ESC

 

"Enter" button (27) and the scroll button (25)

25

to get access to further details.

 

 

27

In case of "LCM WARNING", refer to LCM

 

section (see section 6).

 

 

5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support

LOAD PROTECTED

x.xkVA / xxx% LOADED

x x x x x x x x FAULT

SINGLE UPS

ESC

Press the "Enter" button (27) to display the details below :

 

 

 

 

Displayed details

Signification

Correction

 

 

 

NO BATTERY

The battery is incorrectly connected

Check battery connections

 

 

 

I/O BAD CONNECTION

AC source is not connected to the correct

Check AC wiring

 

terminals

 

 

 

 

NO POWER MODULE

The power sub-module is not inserted

Check power sub-module connections (see

 

 

section 7.1)

 

 

 

NO BATTERY MODULE

The battery sub-module is incorrectly

Check battery connections (see section 7.2)

 

connected

 

 

 

 

INV THERM OVERLOAD

The UPS shuts down automatically because

Check the power drawn by the connected

 

of a major overload.

devices and disconnect any non-priority

 

 

devices.

 

 

 

INVERT LIMITATION

Short circuit conditions on output devices

Check the installation at the UPS output

 

 

(wiring, fault equipment)

 

 

 