4. Access to measurements and personalisation data
Battery settings
Function | Factory setting | Options | Comments |
|
|
|
|
Auto Battery Test | Everyweek | No test / everyday / |
|
|
| everyweek /everymonth |
|
|
|
|
|
Low Batt Warning | 20% | 0 to 100% | 1% increment |
|
|
|
|
User Batt Settings | UPS reads number of | From 0 to 40 Ah | 5 Ah increment |
| battery modules |
|
|
| connected |
|
|
|
|
|
|
Deep Disch Protect | Yes | No | Protection against deep discharge. |
|
|
| If disable, MGE UPS SYSTEMS |
|
|
| warranty will be void |
|
|
|
|
4.5 Maintenance
Function | Option / Display | Comments | |
|
|
|
|
Model | Power Module | SN: xxxxxxxxx | Serial number |
|
| SOFT: xxx | Soft version |
| Frame | ||
| NT: xxx | Technical level | |
|
| ||
|
|
|
|
Alarm History | Read | Description | 10 alarms can be stored |
|
| Date Hour | automatically |
|
| Alarm xxx |
|
|
|
|
|
| Erase | No / Yes |
|
|
|
|
|
Manual Batt Test | Manual Battery Test | No / Yes |
|
|
|
|
|
Led & Buzzer Test | Led & Buzzer Test | No / Yes |
|
|
|
|
|
Life Cycle Monitoring | LCM | Enable / Disable | Life cycling monitoring alarms |
|
|
|
|
Statistics | Auto Statistics | Statistics | You need to register at |
|
|
| www.mgeups.com/Icm to get the |
| Custom Statistics | Reset Date ? | |
| code and get access to free statistics | ||
|
| Are you sure ? | |
|
|
| |
|
|
|
|
Operation Limits | Operation Limits |
| Automatic alarms displayed when |
|
|
| UPS is operating near the limits |
|
|
|
|
4.6Personalisation using external software
◗Insert the
◗On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
◗Then select "Settings", "Advanced settings" and "UPS settings".
Note that only the Windows versions of the Personal