4. Access to measurements and personalisation data

Battery settings

Function

Factory setting

Options

Comments

 

 

 

 

Auto Battery Test

Everyweek

No test / everyday /

 

 

 

everyweek /everymonth

 

 

 

 

 

Low Batt Warning

20%

0 to 100%

1% increment

 

 

 

 

User Batt Settings

UPS reads number of

From 0 to 40 Ah

5 Ah increment

 

battery modules

 

 

 

connected

 

 

 

 

 

 

Deep Disch Protect

Yes

No

Protection against deep discharge.

 

 

 

If disable, MGE UPS SYSTEMS

 

 

 

warranty will be void

 

 

 

 

4.5 Maintenance

Function

Sub-Function

Option / Display

Comments

 

 

 

 

Model

Power Module

SN: xxxxxxxxx

Serial number

 

 

SOFT: xxx

Soft version

 

Frame

 

NT: xxx

Technical level

 

 

 

 

 

 

Alarm History

Read

Description

10 alarms can be stored

 

 

Date Hour

automatically

 

 

Alarm xxx

 

 

 

 

 

 

Erase

No / Yes

 

 

 

 

 

Manual Batt Test

Manual Battery Test

No / Yes

 

 

 

 

 

Led & Buzzer Test

Led & Buzzer Test

No / Yes

 

 

 

 

 

Life Cycle Monitoring

LCM

Enable / Disable

Life cycling monitoring alarms

 

 

 

 

Statistics

Auto Statistics

Statistics

You need to register at

 

 

 

www.mgeups.com/Icm to get the

 

Custom Statistics

Reset Date ?

 

code and get access to free statistics

 

 

Are you sure ?

 

 

 

 

 

 

 

Operation Limits

Operation Limits

 

Automatic alarms displayed when

 

 

 

UPS is operating near the limits

 

 

 

 

4.6Personalisation using external software

Insert the Solution-PacCD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pacsoftware.

Then select "Settings", "Advanced settings" and "UPS settings".

Note that only the Windows versions of the Personal Solution-Pacsoftware offer this possibility.

34008030EN/AA - Page 27

Page 27
Image 27