Users Manual

1.5.3.1 LED Alphanumeric Indicators

Fourteen alphabetically labeled LEDs provide detailed information on UPS status as follows:

A: Emergency shutdown

This red LED indicates that the emergency power off (EPO) or remote emergency power off (REPO) has been activated. See section 2.11.1, Emergency Shutdown.

B: Rectifier/charger on

This green LED indicates that the rectifier/battery charger is on.

C: Rectifier/charger fault

This red LED indicates an alarm condition within the rectifier/battery charger. it indicates the presence of one of the following fault conditions:

Input circuit breaker Q1 open

Input power protection fuse blown

Rectifier/battery charger over-temperature

Battery charge overcurrent

Battery overvoltage

Rectifier/battery charger control board fault

Power supply board fault

D: Main AC input (mains 1) outside tolerance

This orange LED indicates that the main AC input (mains 1) source is outside tolerance (voltage and/or frequency too high or too low).

E: Reserved for future use.

F: Battery temperature outside tolerance

This orange LED indicates that the ambient temperature of the battery is too high or too low.

G: Battery charging

This orange LED indicates that the battery is being recharged. This LED functions only when the connected battery is of the vented lead-acid type (sealed lead-acid batteries will not activate this signal).

H: Inverter fault

This red LED indicates an alarm condition in the inverter, which may be one or more of the following conditions:

Inverter shutdown due to output voltage out of tolerance

Inverter output protection fuse blown

Inverter leg fault

Inverter output transformer over-temperature

Inverter leg over-temperature

Internal clock fault

Inverter control board fault

Power supply board fault

Introduction

page 1 — 11

Page 21
Image 21
MGE UPS Systems EPS 7000 user manual LED Alphanumeric Indicators, Reserved for future use