Trouble

 

Remedy

 

 

 

Low CV weld output.

 

Set Ampere Range switch to highest range.

 

 

 

 

 

Increase Voltage/Amperage Adjust Control setting.

 

 

 

Min or max CV weld output only.

 

Check position of Voltage/Amperage Adjust control and Voltage/Amperage Adjust switch.

 

 

 

 

 

Repair or replace remote control device.

 

 

 

 

 

Have Factory Authorized Service Agent check Amperage/Voltage Adjust Control R1, and field current

 

 

regulator board PC1.

 

 

 

C. Standard Generator Power

 

Trouble

Remedy

 

 

No generator power output at ac recep-

Reset receptacle supplementary protectors.

tacles; weld output okay.

 

 

 

 

Reset GFCI receptacle.

 

 

No generator power or weld output.

Disconnect equipment from generator power receptacles during start-up.

 

 

 

Check fuses F1 and F2, and replace if open (see Section 9-8or 10-9). Have Factory Authorized Service

 

Agent check integrated rectifier SR1, capacitor C9, and the rotor.

 

 

 

Reset supplementary protector CB12. Have Factory Authorized Service Agent check diode D1 .

 

 

 

Have Factory Authorized Service Agent check brushes and slip rings, and field excitation circuit.

 

 

High output at generator power ac re-

Check engine speed, and adjust if necessary.

ceptacles.

 

 

 

 

Have Factory Authorized Service Agent adjust generator power field current resistor R3.

 

 

Low output at generator power ac recep-

Check engine speed, and adjust if necessary.

tacles.

 

 

 

 

Check fuse F1, and replace if open (see Section 9-8or 10-9). Have Factory Authorized Service Agent

 

check integrated rectifier SR1, resistor R3, and capacitor C9.

 

 

D. Optional Three-Phase Generator Power (CC/CV Models Only)

Trouble

Remedy

 

 

No or low output at optional three-

Place Process/Contactor switch in Weld Terminals Always On - Stick position (see Section 7-3).

phase generator/receptacle RC5.

 

 

 

 

Reset supplementary protector CB7(see Section 8-2).

 

 

 

Reset supplementary protector CB5 (see Section 9-8or 10-9).

 

 

 

Check engine weld/power speed, and adjust if necessary (see Section 9-6or 10-6).

 

 

 

Have Factory Authorized Service Agent check brushes and slip rings, and field current regulator board

 

PC1.

 

 

High output at optional three-phase

Check engine weld/power speed, and adjust if necessary (see Section 9-6or 10-6).

generator/receptacle RC5.

 

 

 

 

Have Factory Authorized Service Agent check field current regulator board PC1, and PC1 voltage

 

feedback circuit.

 

 

Erratic output at optional three-phase

Have Factory Authorized Service Agent check brushes and slip rings, and field current regulator board

generator/receptacle RC5.

PC1.

 

 

OM-4428 Page 60