8-2. Connecting To Optional Three-Phase Generator (CC/CV Models Only)

 

 

 

. Place Process/Contactor switch

 

 

 

in Electrode Hot - Stick position

 

 

 

when using three−phase genera-

Single-Phase Power Connection

1

2

tor (see Section 7-3).

Single-Phase Generator Power

 

 

 

 

 

 

1 120/240 V 50 A Receptacle

 

 

 

RC5

 

 

 

RC5 is connected to the optional

 

 

 

three−phase generator and supplies

 

 

 

60 Hz single-phase power at weld/

 

 

 

power speed. Maximum output from

 

 

 

RC5 is 12 kVA/kW. Power available

 

 

 

at RC5 is reduced when welding.

 

 

 

2 Circuit Breaker CB7

 

 

 

Circuit breaker CB7 protects single-

 

 

 

phase receptacle RC5 and the load

 

 

 

wires from overload. If CB7 opens, all

 

 

 

three−phase generator output stops

 

 

 

and the receptacle does not work.

Three-Phase Power Connection

Y Close panel opening if no connections are made to generator.

AC

Single

Three

Phase

Phase

Output

 

1

3

Volts

120/240

240

 

 

 

Amps

50

36

KVA/KW

12

15

Frequency

60 Hz

Engine Speed

1850 RPM

 

 

 

Lead 42 connects to GROUND stud on front of unit.

Jumper 42 is connected to 90 at factory.

93

Three-Phase Generator Power

YStop engine.

YPower and weld outputs are live at the same time. Discon- nect or insulate unused cables.

.Have qualified person install ac-

cording to circuit diagram and Generator Power Guidelines (see Section 12).

Remove generator power panel mounting screws. Tilt panel forward.

3 Lead 93

Remove plug before inserting leads. Reinstall bushing.

5

Rear Of Panel

914 Lead 92

5 Lead 91

906 Lead 42 (Circuit Grounding Lead)

4

92

7

Lead 90 (Neutral)

 

8

Isolated Neutral Terminal

 

 

6

7

9

8

91

92

93

240V

120V

1-Phase

120V

 

 

240V

240V

3-Phase

 

240V

3

2

12

10

11

Y Close panel opening if no connections are made to generator.

Tools Needed:

9Jumper Lead 42

10Grounding Terminal

Jumper 42 is connected to lead 90 at factory. Jumper 42 may be discon- nected from neutral to meet applica- ble electrical codes.

Lead 42 connects to front panel Ground stud.

11User-Supplied Leads

12Circuit Breaker CB7 User Terminals

Connect user-supplied leads to ter- minals on CB7 and to the isolated neutral terminal and grounding termi- nal as necessary.

.Circuit breaker CB7 protects

single-phase receptacle RC5 and the load wires from overload. If CB7 opens, all three−phase generator output stops and the receptacle does not work.

Reinstall generator power panel.

Ref. 197 399 / 802 332-E