9-8. Overload Protection

 

 

 

Y Stop engine.

 

 

 

. When a circuit breaker or fuse

 

 

 

 

opens, it usually indicates a

 

 

 

 

more serious problem exists.

 

 

 

 

Contact Factory Authorized

 

 

 

 

Service Agent.

 

 

 

1

Fuse F1

 

 

 

2

Fuse F2

 

 

 

F1 and F2 protect the stator exciter

 

 

 

winding from overload. If F1 opens,

 

 

 

weld and generator power is low or

 

 

 

stops entirely. If F2 opens, weld out-

 

 

 

put is low or stops entirely. 4 kVA/kW

 

 

 

generator power is still available.

 

2

1

3

Circuit Breaker CB4 (Not

 

 

 

 

Shown)

 

 

 

4

Circuit Breaker CB5

 

 

 

 

(CC/CV Models Only)

 

 

 

5

Circuit Breaker CB6

 

 

 

 

(CC/CV Models Only)

 

 

 

6 Circuit Breaker CB10 (Not

 

9

 

 

Shown)

 

8

 

7

Circuit Breaker CB11

 

7

 

 

 

8

Circuit Breaker CB12

 

 

 

 

 

 

9

Circuit Breaker CB13

 

 

 

CB4 protects the welding arc drive

 

 

 

(dig) circuit. If CB4 opens, electrode

 

 

 

may stick to the workpiece more fre-

 

 

 

quently during low voltage (short arc

 

 

 

length) conditions. CB4 automatical-

 

 

 

ly resets when the fault is corrected.

 

 

 

CB5 protects the 24 volt ac output to

4

5

 

remote receptacle RC14, and 24 volt

 

 

 

output to field current regulator board

 

 

 

PC1 (CC/CV models only). If CB5

 

 

 

opens, weld output and 24 volt out-

 

 

 

put to RC14 stops. On units with op-

 

 

 

tional three−phase generator, gener-

 

 

 

ator power output at receptacle RC5

 

 

 

also stops if CB5 opens.

 

 

 

CB6 protects the 115 volt ac output

 

 

 

to remote receptacle RC14 (CC/CV

 

 

 

models only). If CB6 opens, 115 volt

 

 

 

output to RC14 stops.

 

 

 

CB10 protects the engine battery cir-

 

 

 

cuit. If CB10 opens, the engine will

 

 

 

not crank. CB10 automatically re-

 

 

 

sets when the fault is corrected.

 

 

 

CB11 protects the engine wiring har-

 

 

 

ness. On CC models, if CB11 opens

 

 

 

the max OCV circuit does not work

 

 

 

and open circuit voltage is variable at

 

 

 

all times (see max OCV note under

 

 

 

Weld Controls in Section 6-2). If

 

 

 

CB11 opens on CV models, weld

 

 

 

output stops (generator power is still

 

 

 

available).

 

 

 

CB12 protects the field flashing cir-

 

 

 

cuit. If CB12 opens, the generator

 

 

 

may not excite at start-up and weld

 

 

 

and generator power output may not

 

 

 

be available.

 

 

 

CB13 protects the engine shutdown

 

 

 

circuit. If CB13 opens, the engine

 

 

 

cranks but does not start.

 

 

 

Press button to reset breaker.

 

 

 

 

802 170-D / Ref. 802 311

OM-4406 Page 48