B. Generator Power
Trouble | Remedy |
|
|
No output at generator power ac recep- | Reset receptacle circuit breakers (see Section |
tacles. |
|
|
|
| Press GFCI reset button on 120 volt GFCI receptacles (see Section |
|
|
| Check fuse F1, and replace if open (see Section |
|
|
| Check receptacle(s) for continuity and proper connections. Replace receptacle(s) if necessary. |
|
|
| Have Factory Authorized Service Agent check brushes and slip rings. |
|
|
High or low output at generator power ac | Check engine speed, and adjust if necessary (see Section |
receptacles. |
|
|
|
C. Engine
Trouble | Remedy |
|
|
Engine will not crank. | Check battery voltage, and replace battery if necessary. |
|
|
| Check battery connections and tighten if necessary. |
|
|
| Have Factory Authorized Service Agent check Engine Start Button PB1. |
|
|
Engine cranks but does not start. | Check fuel level (see Section |
|
|
| Open fuel valve (see Section |
|
|
| Check battery voltage, and replace battery if necessary. |
|
|
| Check blower fan |
| loose (see Section |
|
|
| Check engine charging system according to engine manual. |
|
|
| See engine manual. |
|
|
Engine suddenly stops. | Check blower fan |
| loose (see Section |
|
|
| See engine manual. |
|
|
Battery discharges between uses. | Clean battery, terminals, and posts with baking soda and water solution; rinse with clear water. |
|
|
| Periodically recharge battery (approximately every 3 months). |
|
|
| Replace battery. |
|
|
| Check voltage regulator and connections according to engine manual. |
|
|
Engine uses oil during | Dry engine (see Section 10). |
wetstacking occurs. |
|
|
|