1 Foreword

1 Foreword

1.1 Introduction of Maintenance Tools

The Maintenance Tools are comprised of the On-Line Monitor and the Off-Line Monitor. The following two connection methods are available in the Online Monitoring.

(1)Monitoring by connecting the maintenance tool to MN converter (CMS-MNF) via RS-232C.

(2)Monitoring through the central controller (G-50) by connecting the maintenance tool to LAN. A brief explanation of each of their function is provided here.

*To use the maintenance tool via G-50 (Network), license registration for the G-50 to be used is necessary. Purchasing the license No. for each G-50 to be used, conduct the license registration through the Web browser (http://[IP address of the G-50A]/ administrator.html). After selecting "Maintenance tool" of the optional function on the Web Browser Screen displayed, enter the purchased license No..

For the detail of the license registration, see Chapter 4 [Registering a License for Optional Functions] of Central Controller Model: G-50A Web Browser Operation Manual (For manager).

1.1.1 On-Line Monitor(via MN converter)

The On-Line Monitor is connected to the unit by a MN Converter (CMS-MNF) and can monitor such areas as system data, unit data and operating data.

(1) In case for local connection

Connecting PC installed with the maintenance tool to M-NET transmission line via MN Converter allows conducting various monitoring and setting from the maintenance tool.

RS-232C M-NETM-NET

Maintenance

MN Converter

Tools PC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2) In case for remote connection

Using a modem and remotely connecting PC installed with the maintenance tool to MN Converter via public telephone circuit allow conducting various monitoring and setting as same in the case of local connection.

Public

network

RS-232C

RS-232C M-NET

MODEM

MODEM MN Converter

Maintenance

 

Tools PC

 

*For the remote connection utilizing MN Converter, an isolator is required to be inserted between the modem and MN Converter.

For detail, please see Installation Manual-annexing of MN Converter (CMS-MNF).