A[**]appears in the unit address button for

Interference caused an non-existing unit

Wait a moment and then click on the

a unit that does not exist.

to appear.

address button for the same unit again.

 

 

The[**] display will disappear.

 

 

 

A[??]appears in the address button.

There is a unit that is not compatible with

Refer to the explanation on terminology in

 

the maintenance tools.

help.

 

 

If there is no explanation, the unit is not a

 

 

compatible type.

 

 

 

Address searching takes 3 minutes or

The port required for communication is

In this case, the communication

more per set. (G-50 connection)

being protected by the Firewall checking

transmitted from G-50 may not partially be

 

function of Windows or anti-virus

received. Please remove the check mark

 

software.

on the Firewall function of the necessary

 

 

port. (For detail, please refer to Page 57.)

 

 

(If the version of G-50 is more than 2.50,

 

 

only [IC] can be searched, even if it uses

 

 

FIREWALL. However, [OC] reference

 

 

cannot be performed. Moreover, since

 

 

other functions cannot operate normally,

 

 

please be sure to remove a check.)

 

When a maintenance tool is not ended

In this case, please perform "Stop mail

 

normally, G-50 will be in a data resending

communication" of 3.4 (2), and start a

 

state, and LAN communication will

maintenance tool again after waiting

 

increase.

about 15 minutes.

 

The version of G-50 is old.

A recommendation version is 2.50 or

 

 

more.

 

 

 

Connecting information Trouble

Trouble

Cause

Repair

 

 

Cannot switch to connection information

A unit other than an outdoor unit (OC) has

Refer to 3.6.1

screen.

been selected.

 

The connection data display does not

An operating SC other than remote

Click on remote control.

appear when the operating system SC is

control has been clicked.

Monitoring of connection data cannot be

clicked.

 

done from operating SC other than

 

 

remote control.

 

 

 

Operation Monitor Trouble

Trouble

Cause

Repair

 

 

 

The monitor display screen on the

Because of the increased re-transmission

Please take a countermeasure against

operation monitor has red characters.

process work due to abundant

the communication noise source in this

 

communication noise, data may not be

case.

 

monitored fully within the rated cycle.

 

All of the characters on the monitor

There is no answer from the unit.(Cannot

Error with unit.

display for some units are red.

communicate with the unit.)

Refer to the service handbook for that

 

 

unit.

The message of ” G50 can't Connect to

The dial-up router is not connected. Or

By referring to Instruction Manual of

SMTP Server !

connected but incorrectly.

Dial-up router, connect or set correctly.

or G-50 Date Setting is wrong !!

The default gateway of G-50A is not set.

Set correctly by using the G-50A initial

Continue ?” is displayed at remote

monitor setting.

 

setting tool. (Refer to Instruction Manual

 

 

of G-50A initial setting tool.)

 

The incorrect display of the receiver

Set the correct mailing address.

 

address is pointed out by SMTP.

 

 

The Monitor Finish Date is older than the

Set the monitor finish date correctly.

 

current date/time of G-50A.

(However when connecting to G-50A in a

 

 

region with a time differential, set it by

 

 

considering the time in that place.)

A message of " Monitor data size is very

The memory capacity to store data is

Move to Offline Screen, and delete

65

Page 66
Image 66
Mitsubishi G-50A, MN Converter manual Connecting information Trouble, Operation Monitor Trouble

G-50A, MN Converter specifications

The Mitsubishi MN Converter, G-50A, represents a significant advancement in power conversion technology, designed to meet the rigorous demands of various industrial applications. This converter excels in delivering efficient and reliable performance while addressing specific user requirements.

One of the standout features of the G-50A is its high efficiency, typically exceeding 95%. This efficiency minimizes energy losses during the conversion process, significantly reducing operational costs and enhancing the overall economic viability of power-intensive operations. Its robust design ensures that it can handle fluctuating loads, making it suitable for diverse environments, from manufacturing plants to renewable energy systems.

The G-50A employs advanced digital signal processing (DSP) technology, enabling precise control of power conversion processes. This feature not only enhances the converter's performance but also allows for adaptive control strategies that can optimize energy use based on real-time conditions. As a result, users can experience improved reliability and performance consistency over time.

Thermal management is another critical characteristic of the G-50A. It utilizes a sophisticated cooling system that manages the heat generated during operation, ensuring that the unit remains within optimal temperature ranges. This prevents overheating and extends the lifespan of the converter, which is essential for maintaining operational uptime in demanding applications.

The modular design of the G-50A facilitates easier maintenance and scalability. Users can easily replace or upgrade individual components without the need for extensive downtime, significantly improving overall operational efficiency. Moreover, the compact footprint of the G-50A allows for flexible installation in various settings, making it adaptable to space-constrained environments.

In addition to its state-of-the-art technologies and features, the G-50A adheres to stringent international standards for safety and environmental compliance. This ensures that users can operate the converter with confidence, knowing that it meets necessary regulations while minimizing their environmental impact.

Overall, the Mitsubishi MN Converter, G-50A, combines high efficiency, advanced digital technology, and robust design attributes to provide a versatile and reliable power solution for a wide range of applications. Whether integrating into existing systems or establishing new processes, the G-50A stands as an innovative choice for enterprises seeking to optimize energy usage and enhance operational performance.