OC194-24

w8—9 Refer to page OC194-23.

w12 When room temperature is 64°F or below, the compressor cannot operate.

When room temperature rises over 64°F the compressor starts after a 3-minute time delay.

w13 Compressor ON time is decided by room temperature.Refer to page OC194-29.

w14 In dry operation, compressor ON makes the fan speed LOW.Also, when the compressor OFF and the pipe temperature

is 79°F or less, the fan stops, or when the compressor OFF and the pipe temperature is below 43°F the fan speed

changes to LOW mode.

It is not possible to set the fan speed with the remote controller

DRY OPERATION
DRY
operation
Initial dry
operation
Room temperature is
64-F or lower
During
compressor ON
Compressor &
thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w14 w14
w13
YES
YES NO
YES NO
NO
w9
YES
YES
w9
NO
NO
w12
YES
NO
YES w8