OC194-29
<DRY operation time chart>
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Compressor
ON
ON
DRY MODE DRY MODE
ON
OFF
OFF
ON
OFF
3 minutes
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRY operation
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0°F or more, or
lower than 2°F.
3The compressor stops in check mode or during protective functions.
<How to operate>
1Press POWER ON/OFF button.
2Press the MODE button to display “DRY”
3Press the SET TEMP.button to set the desired temperature.
NOTE:The set temperature changes 2°F when the SET TEMP.
button is pressed one time.
Dry 64 to 86°F