OC194-26
2. INDOOR UNIT CONTROL

2-1 COOL operation

(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0 degrees or more,
or lower than 2 degrees.
3The compressor stops in check mode or during protective functions.
4Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 34°F or below after the
compressor has been continuously operated for at least 16 minutes or more.When the indoor coil temperature rises to 50°F
or above, the compressor will start in a 3-minute(w2) time delay.
w2 When the indoor coil temperature is 30°F or less, the compressor starts in 6 minutes.
NOTE :By tur ning OFF the dip switch SW1-3 on indoor controller board, the start temperature of coil frost prevention changes
from 34°F to 36°F.
<How to operate>
1Press POWER ON/OFF button.
2Press the MODE button to display COOL.
3Press the SETTEMP. button to set the desired temperature.
NOTE:Set temperature changes 2°F when the SET TEMP.button
is pressed one time.
Cooling 65 to 87°F.
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Compressor
ON
ON
LOW or HIGH LOW or HIGH
ON
OFF
OFF
ON
OFF
3 minutes
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.

<COOL operation time chart>

w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.