OC194-36
11 TROUBLESHOOTING
The display “CENTRALLY
CONTROLLED”on remote
controller does not disap-
pear.
1) Wrong address setting of remote con-
troller/indoor controller board.
2) Timer adapter is connected to the
remote controller.
3) Signal transmission error between
indoor unit and remote controller.
1) Check the address setting of remote controller
and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2Connect the sub controller to the unit, and
turn circuit breaker ON.
If the display “centrally controlled”disap-
pears, replace the original remote controller.
If the display remains the same, replace the
indoor controller board.
When remote controller
POWER button is turned
ON, the check code
“E0”appears.
1) Signal transmission error between
indoor unit and remote controller 1) 1Connect a sub remote controller.
2Turn circuit breaker ON.
If the display “centrally controlled”remains,
replace the indoor controller board.
3If the display disappears, turn the remote
controller POWER button ON and check as
follows.
When remote controller
POWER button is turned
ON, operating display
appears, but disappears
soon.
1) Short circuit of indoor/outdoor connect-
ing wire
2) Short circuit of transmission wire.
3) Wrong operation of remote controller
due to noise wave emitted by other
appliances.
1), 2) Check the wire
3) Turn the circuit breaker OFF, and then turn ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor
controller board.
Despite turning POWER
button ON, the remote
controller display does not
appear.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged power board.
6) Bad contact of CN2D.
7) Blown fuse.
8) Circuit breaker OFF.
1) Measure the voltage between terminals of
remote controller.If no voltage, remove the ter-
minals and measure the voltage between
wires.If the voltage is between 6VDC and 12V,
replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor
controller board.

1.TROUBLES IN TEST RUN

1
2
3
4
Remote controller
Operating Display
Operating Display
No Display
No Display
Sub remote controller
E0 Display
Operating Display
E0 Display
Operating Display
Malfunction
Malfunction of
indoor Unit
Malfunction of
Remote controller
Malfunction of
indoor Unit and
Remote Controller
Malfunction of
Remote controller
Symptom Cause Check points