7 - 30 7 - 30

MELSEC-Q
7 ONLINE MODULE CHANGE

(b) The "Online module change completed" scree n appears.

7.4 Range Reference Table

The range reference tables are given below.

(1) Reference table for offset/gain values of industrial shipmentsettings (buffer memory addresses 202 to 233: Un\G202 to 233)(a) For Q64AD

The reference values change depending on the setting of the pass data

classification setting (buffer memory address 200: Un\G200).

Address (Decimal)
CH1 CH2 CH3 CH4 Description Pass data classification
setting
Reference value
(Hexadecimal)
Voltage specified Approx. 800CH
202 204 206 208 Industrial shipment settings offset value Current specified Approx. 800CH
Voltage specified Approx. FA64H
203 205 207 209 Industrial shipment settings gain value Current specified Approx. BD38H
(b) For Q68ADV
Address (Decimal)
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Description Reference value
(Hexadecimal)
202 204 206 208 210 212 214 216 Industrial shipment settings offset value Approx. 800CH
203 205 207 209 211 213 215 217 Industrial shipment settings gain value Approx. FA64H
(c) For Q68ADI
Address (Decimal)
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Description Reference value
(Hexadecimal)
202 204 206 208 210 212 214 216 Industrial shipment settings offset value Approx. 800CH
203 205 207 209 211 213 215 217 Industrial shipment settings gain value Approx. BD38H