6 - 4 6 - 4

MELSEC-Q
6 PROGRAMMING
6.2 Programming Example without Using the Utility Package(1) Programming example using the FROM/TO commands
Set the A/D conversion enabled channel (initial setting)
0
X10
139
Error
reset
signal
X0F
Error
flag
170 END
Read digital output values for
CH1 to 3
X0
Module
READY
Error code display and reset processing
BCD D14 K3Y20
Error code
SET Y0F
Error clear
request
Y0F
167
Error
clear
request
X0F
Error
flag
RST Y0F
Error clear
request
Output the error code to Y20
to Y2B by BCD code.
T0 H0 K1K0 H8 CH1 to CH3 are A/D conversion
enabled
T0 H0 K1K2 K50 Set the average number of times
for CH2 to 50 times
T0 H0 K1K3 K1000 Set the average time for CH3 to
1000 ms
T0 H0 K1K9 H604 Specify averaging processing
Y9SETOperating
condition
setting request
Y9
101
Operating
condition
setting
request
X9
Operating
condition
setting completed
RST Y9
Operating
condition
setting request
X11
104
Read
digital
values
X0
Module
READY CH1
Digital
output
Digital output value read processing
X0E
A/D
conversion
completed
flag
FROM H0 K1K11 D11
CH2
Digital
output
FROM H0 K1K12 D12
CH3
Digital
output
FROM H0 K1K13 D13
Error code
FROM H0 K1K19 D14
Set Y9 (operating condition
setting request) from ON to OFF
and enable the initial setting
Clear the error code.