5 - 12 5 - 12
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-AD)
5.4 Initial Setting
[Purpose of setting]
The following A/D initial setting parameters are set:
• A/D conversion enable/disable setting
• Sampling process/averaging process setting
• Time/number of times specifying
• Average time/average number of times settin g
By performing these initial settings, the sequence program settings are not required.
[Startup procedure]
"Start I/O No. " "Package name" "Module model name" Initial setting
[Setting screen]
[Explanation of items]
(1) Setting contents
Set whether A/D conversion is enabled or disabled and the A/D convers ion
method for each channel.
(2) Explanation of command buttons
Make text file Outputs the screen display in text file format.
End setup Confirms the setting data and ends the operati on.
Cancel Cancels the setting data and ends the operatio n.
POINT
Initial settings are stored in the intellig ent function module parameters. After the
initial settings are written to the CPU module, they are validate d by operating the
RUN-STOP switch as follows, STOP RUN STOP RUN, turning the power
OFF and then ON, or resetting the CPU module.
When using a sequencer program to write the initial settings, when the CPU is
switched from STOP to RUN the initial settin gs will be written, So ensures that
programming is carried out to re-execute the initial settings.