ELECTRICAL WIRING

CONNECTING REMOTE RECEIVER

THESE INSTRUCTIONS SUPERCEDE THE SECTION ENTITLED “HEARTH MOUNT” IN THE MILLI-VOLT HAND-HELD REMOTE INSTRUCTIONS SUPPLIED WITH THE REMOTE.

1.Remove cover on control panel to show opening for remote receiver. See Figure 18.

2.Connect the remote connectors located in the unit.

3.Slide remote receiver in the opening of control panel. Use two screws provided to attach remote receiver to the control panel. See Figure 18.

4.Replace Cover.

NOTE: Do not place remote in combustion chamber.

Remote

Receiver

Cover

Figure 18 - Installing Remote Receiver

CHECKING SYSTEM OPERATION

The milli-volt system and individual components may be checked with a milli- volt meter having a 0-1000 mV range. Conduct each check shown in chart below by connection meter test leads to terminals as indicated.

 

 

CONNECT

SWITCH OR

 

 

CHECK

TO

METER

THERMOSTAT

METER

 

TEST

TEST

LEADS TO

CONTACTS

READING

 

 

 

TERMINALS

 

SHOULD BE

 

A

COMPLETE

2 & 3

CLOSED

CLOSED

 

 

SYSTEM

 

 

 

 

 

 

 

 

 

 

B

THERMOPILE

1 & 2

OPEN

OPEN

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

A.COMPLETE MILLI-VOLT SYSTEM CHECK

(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)

a.If the reading is more than 100 milli-volts and the automatic valve still does not come on, replace the control.

b.If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading, proceed to Section B below.

B.Thermopile Output Reading Check

(“B” Reading - Thermostat contacts OPEN - Main burner OFF)

1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.

20

71D0532

Page 20
Image 20
Monessen Hearth DFS32NVC, DFS36NVC Connecting Remote Receiver, Checking System Operation, Complete MILLI-VOLT System Check