DCA-25SSAI — OUTPUT VOLTAGE SETUP

240/120V Hard Wire Hookup

With the voltage selector set and locked at ‘single phase 240/120’ and using single phase 120 volts, it will provide three legs available with 100 amps each on three different circuits (Figure 16).

When using single phase 240 volts, it will provide one leg with 50 amps available (Figure 16).

480/240V Hard Wire Hookup

With the voltage selector set and locked at ‘3 phase 480/ 277’ (Figure 17) and using the 3-phase 240 volt hookup, it will provide one circuit available at 108 amps with any two wires plus the ground (Figure 18).

When using the 3-phase 480 volts hookup, it will provide one circuit available at 50 amps available with all three wires plus ground (Figure 18).

FIGURE 17. Voltage Selector Switch 480/277V Three Phase

Position

FIGURE 16. Hard Wire Hookup at 240/120V Position

FIGURE 18. Hard Wire Hookup For 240V or 480V

PAGE 32 — DCA-25SSAI — PARTS AND OPERATION MANUAL—FINAL COPY (06/30/01)

Page 32
Image 32
Multiquip operation manual DCA-25SSAI Output Voltage Setup, 240/120V Hard Wire Hookup