DCA-25SSAI — OUTPUTTERMINAL PANEL
Output Terminal Panel
The output control panel is located on the rear (control panel) end of the generator. The UVW lugs are protected by a face plate cover that can be secured in the close position by a pad lock.
120 Volt Receptacle
One GFCI Duplex NEMA
The reset button will reset the receptacle after being tripped. Pressing the "Test Button" (See Figure 8) in the center of this receptacle will check the GFCI function. The receptacle should be tested at least once a month.
Connecting Load
Loads can be connected to the generator by the UVW Lugs or the duplex receptacle. (See Figure 9). Make sure to read the operation manual before attempting to connect a load to the generator.
Figure 9. Connecting Loads
Circuit Breakers
To protect the generator from an overload, a
Figure 8. GFCI Test Button | Maximum Output |
| The entire load connected to the UVW l ugs and all four slots in |
| the duplex receptacle must not exceed 22 kW in standby or 20 |
| kW in prime output. |
| 120V Receptacles - These receptacles can be used |
| anytime the generator is in operation. They are controlled |
| by the circuit breakers above them. |
| Twist Lock Dual Voltage Receptacles - To use these |
| receptacles, place the voltage selector switch in the single |
| phase 240/120 voltage position and adjust the output |
| voltage to 240 volts with the voltage regulator on the |
| control panel (see Figure 6, page 24). Place the voltmeter |
| |
|
PAGE 28 —