Battery

This unit is of negative ground. DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level is not properly maintained. Add only distilled water when replenishment is necessary. DO NOT over fill.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with a thin film of grease will help to inhibit corrosion.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 33) are properly connected to the battery terminals as shown below.The RED cable is connected to the positive terminal of the battery, and the BLACK cable is connected to the negative terminal of the battery.

Figure 33. Battery Connections

DCA-25SSAIPRE-SETUP

CAUTION :

If the battery cable is connected incorrectly, damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

When connecting battery do the following:

1.DO NOT connect the battery cables to the battery terminals when the key is in the ignition and is set in 'START' mode. ALWAYS remove the key from the ignition and the ignition switch is in the OFF position when connecting the battery.

2.Place a small amount of grease around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.

CAUTION :

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

Wiring

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

Piping and Hose Connection

Inspect all piping, oil hose, and fuel hose connections for wear and tightness.Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

PAGE 41 — DCA-25SSAI — PARTS AND OPERATION MANUAL— FINAL COPY (06/29/01)

Page 41
Image 41
Multiquip operation manual DCA-25SSAI PRE-SETUP, Battery Cable Installation, Wiring, Piping and Hose Connection