Multiquip operation manual DCA-25SSAI - GENERATOR START-UP PROCEDURE, Engine Enclosure Doors

Models: DCA-25SSAI

1 142
Download 142 pages 25.18 Kb
Page 44
Image 44
DCA-25SSAI — GENERATOR START-UP PROCEDURE

DCA-25SSAI — GENERATOR START-UP PROCEDURE

4. Close all engine enclosure doors (Figure 37).

Figure 37. Engine Enclosure Doors

5.Check the voltage selection switch (Figure 38) is at the desired voltage.

Figure 38. Voltage Selection Switch

6.Make sure the engine throttle (Figure 39) is in ’start/idle’.

Figure 39. Engine Throttle Lever (low)

7.Turn the ignition key to preheat (Figure 40), until the preheat indicator turns on.

8.Once the preheat indicator lights, turn the ignition key to ‘START’ until the engine starts (Figure 41). Then release the key to ‘RUN’.

Figure 41. Ignition Switch ‘START’

9.Pull the engine throttle and turn to the right until the metal stop rests against the control panel (Figure 42).

Figure 42. Engine Throttle Lever (high)

10.The generator's frequency meter (Figure 43) displays the 60 cycle output frequency in HERTZ.

Figure 43. Frequency Meter (Hz)

11.The generator's voltage meter (Figure 44) displays the 120 VAC in VOLTS. If the voltage is not within the specified frequency tolerance, use the voltage adjustment control knob (Figure 45) to increase or decrease the desired voltage.

Figure 40. Ignition Switch ‘PREHEAT’

Figure 44. Voltage Meter (Volts)

PAGE 44 — DCA-25SSAI — PARTS AND OPERATION MANUAL—FINAL COPY (06/30/01)

Page 44
Image 44
Multiquip operation manual DCA-25SSAI - GENERATOR START-UP PROCEDURE, Engine Enclosure Doors, Voltage Selection Switch